Melola Discovery

← Melola Discovery

Akses terbuka Jurnal SINTA 1

Performance analysis and effect of pandemic condition on utility grid connected PV system

International Journal of Power Electronics and Drive Systems · Vol. 15 No. 1 (2024) · hlm. 160–167

DOI
10.11591/ijpeds.v15.i1.pp160-167
ISSN
2722-256X, 2088-8694
Terbit
2024-03-01
Penerbit
Institute of Advanced Engineering and Science
Bahasa
eng
Lisensi
creativecommons.org/licenses/by-sa/4.0

Abstrak

In this research paper effect of pandemic and performance analysis of the utility grid connected PV system under net metering is evaluated for one years based on PV plant generation data. The performance of the system depends on annual average final yield, reference yield, and array yield and their values are 3.87 kWh kWp-1. d-1, 4.57 kWh kWp-1. d-1, and 4.29 7kWh kWp-1d-1 the performance ratio and capacity utilization factor are 77.48% and 15.68%. Due to pandemic campus energy consumption is less so energy export to grid is more than the energy import from grid. As per the state energy policy minimum billing is done even the export units are more than the imported units which result in increase in return on investment (ROI) compared to post pandemic. The above statistics illustrate the quite strong performance of solar power plants built in the Indian state of the Andhra Pradesh, Guntur.

Kata kunci

Jaringan kolaborasi para penulis

2 penulis · 1 tautan kepenulisan bersama

Arahkan kursor atau ketuk sebuah nama untuk menyorot rekan penulisnya. Klik dua kali untuk membuka halaman penulis.

  • Visvesvaraya Technological University
  • Organisasi berbeda
  • Organisasi sama
  • Afiliasi tidak diketahui
  • Garis lebih tebal = lebih banyak artikel bersama · lingkaran lebih besar = lebih banyak artikel
Tampilkan sebagai tabel
Rekan penulisOrganisasiArtikel bersama

Afiliasi berasal dari OpenAlex; metadata OAI-PMH jurnal tidak memuatnya. Penulis tanpa ID OpenAlex dicocokkan berdasarkan nama, sehingga dua orang bisa tergabung atau satu orang bisa terpisah.

Sumber metadata: OAI-PMH (metadata jurnal) http://ijpeds.iaescore.com/index.php/IJPEDS/oai, pertama di-harvest 8 Nov 2026, terakhir terlihat 22 Nov 2026.
Metadata asli (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/  http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
	<dc:title xml:lang="en-US">Performance analysis and effect of pandemic condition on utility grid connected PV system</dc:title>
	<dc:creator>Battula, Veera Vasantha  Rao</dc:creator>
	<dc:creator>Krishnarao, Padmavathi</dc:creator>
	<dc:subject xml:lang="en-US">performance ratio;  energy yield;  trivector meter;  IoT based energy monitoring; power purchase agreement</dc:subject>
	<dc:description xml:lang="en-US">In this research paper effect of pandemic and performance analysis of the utility grid connected PV system under net metering is evaluated for one years based on PV plant generation data. The performance of the system depends on annual average final yield, reference yield, and array yield and their values are 3.87 kWh kWp-1. d-1, 4.57 kWh kWp-1. d-1, and 4.29 7kWh kWp-1d-1 the performance ratio and capacity utilization factor are 77.48% and 15.68%. Due to pandemic campus energy consumption is less so energy export to grid is more than the energy import from grid. As per the state energy policy minimum billing is done even the export units are more than the imported units which result in increase in return on investment (ROI) compared to post pandemic. The above statistics illustrate the quite strong performance of solar power plants built in the Indian state of the Andhra Pradesh, Guntur.</dc:description>
	<dc:publisher xml:lang="en-US">Institute of Advanced Engineering and Science</dc:publisher>
	<dc:contributor xml:lang="en-US"></dc:contributor>
	<dc:date>2024-03-01</dc:date>
	<dc:type>info:eu-repo/semantics/article</dc:type>
	<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
	<dc:type xml:lang="en-US"></dc:type>
	<dc:format>application/pdf</dc:format>
	<dc:identifier>https://ijpeds.iaescore.com/index.php/IJPEDS/article/view/22783</dc:identifier>
	<dc:identifier>10.11591/ijpeds.v15.i1.pp160-167</dc:identifier>
	<dc:source xml:lang="en-US">International Journal of Power Electronics and Drive Systems (IJPEDS); Vol 15, No 1: March 2024; 160-167</dc:source>
	<dc:source>2722-256X</dc:source>
	<dc:source>2088-8694</dc:source>
	<dc:source>10.11591/ijpeds.v15.i1</dc:source>
	<dc:language>eng</dc:language>
	<dc:relation>https://ijpeds.iaescore.com/index.php/IJPEDS/article/view/22783/14413</dc:relation>
	<dc:rights xml:lang="en-US">Copyright (c) 2023 Veera Vasantha  Rao B, Padmavathi K</dc:rights>
	<dc:rights xml:lang="en-US">http://creativecommons.org/licenses/by-sa/4.0</dc:rights>
</oai_dc:dc>