Microgrids play an essential role in supporting reliable and sustainable energy supply, yet their performance is strongly affected by the intermittency of renewable sources such as photovoltaic and wind systems. These variations introduce nonlinear dynamics that challenge conventional control strategies, particularly in maintaining stable active–reactive power flow and DC-link voltage. This study addresses these challenges by optimizing the Proportional–Integral (PI) controller used in a Voltage Source Converter within a hybrid PV–wind–battery microgrid. The research contribution is the development and benchmarking of a hybrid Spherical Vector Particle Swarm Optimization and Differential Evolution (HSPSO-DE) method for PI tuning to improve dynamic response and overall microgrid performance. The microgrid incorporates standard Perturb-and-Observe MPPT for the PV subsystem and an adaptive P&O variant for wind energy to support improved power harvesting, while the battery system ensures load–generation balance during fluctuations. Simulation analysis demonstrates that the HSPSO-DE-tuned PI controller achieves faster convergence, reduced steady-state error, and lower power oscillations when compared with GA, PSO, and GWO-based tuning. Total Harmonic Distortion results confirm improved power quality and enhanced operational stability. The findings establish the proposed hybrid optimization–based PI control as an effective solution for robust microgrid performance under dynamic and uncertain operating conditions.