Study of Flow Rate Effect on Horizontal Flow Concrete Sand Filter Filtration Performance

Journal of the Civil Engineering Forum · Vol. 10 No. 1 (2023) · hlm. 23–30

DOI
10.22146/jcef.6782
ISSN
2549-5925, 2581-1037
Terbit
2023-12-15
Penerbit
Department of Civil and Environmental Engineering, Faculty of Engineering, Universitas Gadjah Mada
Bahasa
eng

Abstrak

The need for clean water during the pandemic is significantly increasing due to high public awareness of adopting a clean and healthy lifestyle (PHBS), necessitating more water treatment. Conventional methods are used for water treatment, including coagulation-flocculation system, rapid sand filter, and disinfection. However, these methods have limitations such as reduced capacity and sand filter efficiency, leading to increased backwash costs due to the need for sand replacement caused by particle stratification. In response to these challenges, an innovative method to water treatment is the use of concrete sand filter (CSF). Previous studies predominantly focused on downflow filtration, but there has been limited analysis of horizontal flow. Therefore, this study aimed to assess filtration and backwash effectiveness of CSF with horizontal flow, specifically focusing on the capacity performance in treating water with varying levels of turbidity. Filtration experiment was carried out using simulated water at turbidity of 125 NTU based on the Mataram Channel Turbidity with variations of 0.2, 0.5, 1.0, 5.0, and 10.0 m hour-1, as well as backwash at flow rate of 40.91 m hour-1 for 3 minutes. The variables measured during filtration process included head losses and turbidity at the inlet and outlet of CSF. The results showed that the capacity performance during filtration process was directly proportional to flow rate. Meanwhile, the effectiveness of concrete filter was inversely proportional to flow rate. At initial turbidity <617 NTU, the 3 minutes backwash process obtained lower final turbidity compared to the raw water used, which was 5.19 NTU. Meanwhile, at turbidity 617 NTU, the final turbidity was still high, reaching approximately 14.6–26.4 NTU.

Kata kunci

Jaringan kolaborasi para penulis

6 penulis · 9 tautan kepenulisan bersama

Arahkan kursor atau ketuk sebuah nama untuk menyorot rekan penulisnya. Klik dua kali untuk membuka halaman penulis.

  • Universitas Gadjah Mada
  • Organisasi berbeda
  • Organisasi sama
  • Afiliasi tidak diketahui
  • Garis lebih tebal = lebih banyak artikel bersama · lingkaran lebih besar = lebih banyak artikel
Tampilkan sebagai tabel
Rekan penulisOrganisasiArtikel bersama
Syafira Bunga Az ZahraUniversitas Gadjah Mada1
Ni Nyoman Nepi MarleniUniversitas Gadjah Mada1
Hendra DewataUniversitas Gadjah Mada1

Afiliasi berasal dari OpenAlex; metadata OAI-PMH jurnal tidak memuatnya. Penulis tanpa ID OpenAlex dicocokkan berdasarkan nama, sehingga dua orang bisa tergabung atau satu orang bisa terpisah.

Sumber metadata: OAI-PMH (metadata jurnal) https://jurnal.ugm.ac.id/v3/jcef/oai, pertama di-harvest 9 Nov 2026, terakhir terlihat 22 Nov 2026.
Metadata asli (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/  http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
	<dc:title xml:lang="en-US">Study of Flow Rate Effect on Horizontal Flow Concrete Sand Filter Filtration Performance</dc:title>
	<dc:creator>Parsada, Laksmana Angga</dc:creator>
	<dc:creator>Kamulyan, Budi</dc:creator>
	<dc:creator>Triatmadja, Radianta</dc:creator>
	<dc:subject xml:lang="en-US">Filter</dc:subject>
	<dc:subject xml:lang="en-US">Filtration</dc:subject>
	<dc:subject xml:lang="en-US">Rates</dc:subject>
	<dc:subject xml:lang="en-US">Horizontal Turbidity</dc:subject>
	<dc:subject xml:lang="en-US">Water</dc:subject>
	<dc:description xml:lang="en-US">The need for clean water during the pandemic is significantly increasing due to high public awareness of adopting a clean and healthy lifestyle (PHBS), necessitating more water treatment. Conventional methods are used for water treatment, including coagulation-flocculation system, rapid sand filter, and disinfection. However, these methods have limitations such as reduced capacity and sand filter efficiency, leading to increased backwash costs due to the need for sand replacement caused by particle stratification. In response to these challenges, an innovative method to water treatment is the use of concrete sand filter (CSF). Previous studies predominantly focused on downflow filtration, but there has been limited analysis of horizontal flow. Therefore, this study aimed to assess filtration and backwash effectiveness of CSF with horizontal flow, specifically focusing on the capacity performance in treating water with varying levels of turbidity. Filtration experiment was carried out using simulated water at turbidity of 125 NTU based on the Mataram Channel Turbidity with variations of 0.2, 0.5, 1.0, 5.0, and 10.0 m hour-1, as well as backwash at flow rate of 40.91 m hour-1 for 3 minutes. The variables measured during filtration process included head losses and turbidity at the inlet and outlet of CSF. The results showed that the capacity performance during filtration process was directly proportional to flow rate. Meanwhile, the effectiveness of concrete filter was inversely proportional to flow rate. At initial turbidity &amp;lt;617 NTU, the 3 minutes backwash process obtained lower final turbidity compared to the raw water used, which was 5.19 NTU. Meanwhile, at turbidity 617 NTU, the final turbidity was still high, reaching approximately 14.6–26.4 NTU.</dc:description>
	<dc:publisher xml:lang="en-US">Department of Civil and Environmental Engineering, Faculty of Engineering, Universitas Gadjah Mada</dc:publisher>
	<dc:date>2023-12-15</dc:date>
	<dc:type>info:eu-repo/semantics/article</dc:type>
	<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
	<dc:type xml:lang="en-US">Peer-reviewed Article</dc:type>
	<dc:type xml:lang="en-US">'image', 'text'</dc:type>
	<dc:format>application/pdf</dc:format>
	<dc:identifier>https://jurnal.ugm.ac.id/v3/JCEF/article/view/6782</dc:identifier>
	<dc:identifier>10.22146/jcef.6782</dc:identifier>
	<dc:source xml:lang="en-US">Journal of the Civil Engineering Forum; Vol. 10 No. 1 (January 2024); 23-30</dc:source>
	<dc:source>2549-5925</dc:source>
	<dc:source>2581-1037</dc:source>
	<dc:language>eng</dc:language>
	<dc:relation>https://jurnal.ugm.ac.id/v3/JCEF/article/view/6782/3743</dc:relation>
	<dc:rights xml:lang="en-US">Copyright (c) 2024 The Author(s)</dc:rights>
</oai_dc:dc>