Evaluation of the Implementation of the Local Exhaust Ventilation System in the Testing Laboratory

The Indonesian Journal Of Occupational Safety and Health · Vol. 11 No. 1 (2022) · hlm. 83–93

DOI
10.20473/ijosh.v11i1.2022.83-93
ISSN
2540-7872, 2301-8046
Terbit
2022-03-30
Penerbit
Universitas Airlangga
Bahasa
eng
Lisensi
creativecommons.org/licenses/by-nc-sa/4.0

Abstrak

Introduction: One of the ways to control hazards with an engineering approach in an effort to reduce hazards due to chemical reactions in the laboratory is to install a ventilation system, especially in the Atomic Absorption Spectrophotometer (AAS). The research objectives of this study are to evaluate the implementation of the Local Exhaust Ventilation System in the AAS room. Method: This study used a descriptive observational method with a cross-sectional approach. It was carried out at the Testing Laboratory of the Technical Implementation Unit (henceforth-UPT) of Occupational Safety Surabaya. Data collection was carried out through direct observation in the field to determine the LEV system components and to measure the flow velocity in the inlet and outlet areas of the LEV system. The data obtained were analyzed descriptively by describing the situation systematically and factually. The data were then presented in the form of narration, tabulation, and figures. Results: The conditions of the Local Exhaust Ventilation (LEV), in terms of the design, type and material of each component such as the hood, ducting system and pump machine as well as the fan, are already in accordance with the tool specifications and ASHRAE standards. However, the LEV system has not installed an air cleaner. The results of the measurement show that flow velocity in the LEV system has met the standard, which is 10 m/s with the danger of fume contaminants. In fact, its volumetric flow rate has decreased by more than 20%. Conclusion: laboratory management is advised to consider installing an air cleaner on the LEV system installed in the Hitachi AAS so that contaminants released in the air are cleaner and more environmentally friendly.Keywords: hazard control, laboratory, local exhaust ventilation, ventilation

Jaringan kolaborasi para penulis

40 penulis · 132 tautan kepenulisan bersama · 51 lintas organisasi · menampilkan 40 yang paling banyak terhubung

Arahkan kursor atau ketuk sebuah nama untuk menyorot rekan penulisnya. Klik dua kali untuk membuka halaman penulis.

  • Universitas Airlangga
  • Universitas Gadjah Mada
  • Universitas Muslim Indonesia
  • Universiti Teknologi MARA
  • Universitas Sulawesi Tenggara
  • Hasanuddin University
  • Japan Nutrition University
  • Organisasi lain
  • Afiliasi tidak diketahui
  • Organisasi berbeda
  • Organisasi sama
  • Afiliasi tidak diketahui
  • Garis lebih tebal = lebih banyak artikel bersama · lingkaran lebih besar = lebih banyak artikel
Tampilkan sebagai tabel
Rekan penulisOrganisasiArtikel bersama
Dominikus Raditya AtmakaUniversitas Airlangga7
Putri Ayuni AlayyannurUniversitas Airlangga5
Endang DwiyantiUniversitas Airlangga4
Ardyanisa Raihan KusumaUniversitas Airlangga3
Sheila Amara PutriUniversitas Airlangga3
Mutiara Arsya Vidianinggar WijanarkoJapan Nutrition University3
Norfezah Md NorUniversiti Teknologi MARA3
Nadiatul Syima Mohd ShahidUniversiti Teknologi MARA3
Tri MartianaUniversitas Airlangga3
Bian Shabri Putri IrwantoUniversitas Airlangga3
Anisah Firdaus RahmawatiUniversitas Airlangga2
Isas AwwalinaUniversitas Airlangga2
Nala Astari PramestiUniversitas Airlangga2
Indriati PaskariniUniversitas Airlangga2
Dani Nasirul HaqiUniversitas Airlangga2
Devy Syanindita RoshidaGriffith University2
Asri Meidyah AgustinUniversitas Airlangga2
S.Gz, MPH, Dominikus Raditya AtmakaAfiliasi tidak diketahui2
Rusman AmirullahUniversitas Muslim Indonesia1
Hasbi BakriUniversitas Muslim Indonesia1
Muhamad Karnoha AmirUniversitas Sulawesi Tenggara1
Muhammad Ilham KadarUniversitas Halu Oleo1
Agus Ardianto BudimanUniversitas Muslim Indonesia1
Yogi La Ode PrianataUniversitas Sulawesi Tenggara1
Erni AstutikUniversitas Airlangga1
A. ShodiqurrosyadAfiliasi tidak diketahui1
Latifah FakhrurAfiliasi tidak diketahui1
Nur Afi LailiAfiliasi tidak diketahui1
Slamet HartonoUniversitas Gadjah Mada1
Dwidjono Hadi DarwantoUniversitas Gadjah Mada1
Happy Dewi PurnomowatiUniversitas Gadjah Mada1
Jamhari JamhariUniversitas Gadjah Mada1
Defidelwina DefidelwinaUniversitas Pasir Pangaraian1
Lestari Rahayu WaluyatiUniversitas Gadjah Mada1
Sa’idah Zahrotul JannahUniversitas Airlangga1
Anisah Firdausi RahmawatiUniversitas Airlangga1
Dian Prasasti KurniawatiUniversitas Airlangga1

Afiliasi berasal dari OpenAlex; metadata OAI-PMH jurnal tidak memuatnya. Penulis tanpa ID OpenAlex dicocokkan berdasarkan nama, sehingga dua orang bisa tergabung atau satu orang bisa terpisah.

Sumber metadata: OAI-PMH (metadata jurnal) https://e-journal.unair.ac.id/IJOSH/oai, pertama di-harvest 10 Nov 2026, terakhir terlihat 16 Nov 2026.
Metadata asli (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/  http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
	<dc:title xml:lang="en-US">Evaluation of the Implementation of the Local Exhaust Ventilation System in the Testing Laboratory</dc:title>
	<dc:creator>Setyawan, Yudha Andaka</dc:creator>
	<dc:creator>Arini, Shintia Yunita</dc:creator>
	<dc:creator>Widodo, Sri</dc:creator>
	<dc:description xml:lang="en-US">Introduction: One of the ways to control hazards with an engineering approach in an effort to reduce hazards due to chemical reactions in the laboratory is to install a ventilation system, especially in the Atomic Absorption Spectrophotometer (AAS). The research objectives of this study are to evaluate the implementation of the Local Exhaust Ventilation System in the AAS room. Method: This study used a descriptive observational method with a cross-sectional approach. It was carried out at the Testing Laboratory of the Technical Implementation Unit (henceforth-UPT) of Occupational Safety Surabaya. Data collection was carried out through direct observation in the field to determine the LEV system components and to measure the flow velocity in the inlet and outlet areas of the LEV system. The data obtained were analyzed descriptively by describing the situation systematically and factually. The data were then presented in the form of narration, tabulation, and figures. Results: The conditions of the Local Exhaust Ventilation (LEV), in terms of the design, type and material of each component such as the hood, ducting system and pump machine as well as the fan, are already in accordance with the tool specifications and ASHRAE standards. However, the LEV system has not installed an air cleaner. The results of the measurement show that flow velocity in the LEV system has met the standard, which is 10 m/s with the danger of fume contaminants. In fact, its volumetric flow rate has decreased by more than 20%. Conclusion: laboratory management is advised to consider installing an air cleaner on the LEV system installed in the Hitachi AAS so that contaminants released in the air are cleaner and more environmentally friendly.Keywords: hazard control, laboratory, local exhaust ventilation, ventilation</dc:description>
	<dc:publisher xml:lang="en-US">Universitas Airlangga</dc:publisher>
	<dc:date>2022-03-30</dc:date>
	<dc:type>info:eu-repo/semantics/article</dc:type>
	<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
	<dc:type xml:lang="en-US">Peer-reviewed Article</dc:type>
	<dc:format>application/pdf</dc:format>
	<dc:identifier>https://e-journal.unair.ac.id/IJOSH/article/view/25498</dc:identifier>
	<dc:identifier>10.20473/ijosh.v11i1.2022.83-93</dc:identifier>
	<dc:source xml:lang="en-US">The Indonesian Journal of Occupational Safety and Health; Vol. 11 No. 1 (2022): The Indonesian Journal of Occupational Safety and Health; 83-93</dc:source>
	<dc:source>2540-7872</dc:source>
	<dc:source>2301-8046</dc:source>
	<dc:language>eng</dc:language>
	<dc:relation>https://e-journal.unair.ac.id/IJOSH/article/view/25498/pdf</dc:relation>
	<dc:rights xml:lang="en-US">Copyright (c) 2022 The Indonesian Journal Of Occupational Safety and Health</dc:rights>
	<dc:rights xml:lang="en-US">http://creativecommons.org/licenses/by-nc-sa/4.0</dc:rights>
</oai_dc:dc>