Penentuan ukuran pipa kapiler dengan program aplikasi CapSel Versi 1.0 pada AC trainer unit jenis ekspansi langsung dengan R-410A

Journal of Applied Mechanical Engineering and Green Technology · Vol. 3 No. 1 (2022) · hlm. 31–35

DOI
10.31940/jametech.v3i1.31-35
ISSN
2684-8201, 2655-9145
Terbit
2022-03-31
Penerbit
Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali
Bahasa
ind

Abstrak

Inggris

The use of air conditioning system currently mostly uses the vapor compression cycle. One such air conditioning machine is a direct expansion type AC. In this type of air conditioner, the air is directly cooled by the refrigerant. Cold air is flowed through the air duct to be entered into the room to be cooled. The refrigerant used is R-410A which does not contain chlorine so it does not cause depletion of the ozone layer because it has an ODP = 0. This direct expansion unit trainer uses an expansion device in the form of a capillary tube and an external equalizer type TXV. To determine the size of the capillary tube on the trainer unit, the direct expansion type uses the CapSel version 1.0 application program. By using the input data for refrigerant type R-134A, refrigeration capacity 2,637.6 Watt (9000 BTU/hour), evaporation temperature 5 °C condensation temperature 47 °C, and return gas temperature 12 °C, the recommended capillary pipe size data is obtained, namely the length of the pipe. capillary 1.47 m with an inner diameter of 2.50 mm. The test was carried out by varying the velocity of the air leaving the airways at high speed (22.3 ft/s) and at low speed (7.9 ft/s). The refrigerant temperature and pressure data are measured at 4 measurement points and the measurement of the electric current entering the system. After processing the data and entering it into the Coolpack application program, the average COP and EER in the low speed position produce a higher price than the high speed position.

Bahasa Indonesia

Penggunaan mesin pengkondisian udara saat ini paling banyak menggunakan siklus kompresi uap. Salah satu mesin pengkondisian udara tersebut adalah AC jenis ekspansi langsung. Pada AC jenis ini udara langsung didinginkan oleh refrigeran. Udara dingin dialirkan melalui saluran udara untuk dimasukan ke dalam ruangan yang akan didinginkan. Refrigeran yang digunakan adalah R-410A yang tidak mengandung unsur khlor sehingga tidak menyebabkan penipisan lapisan ozon karena mempunyai ODP = 0. Trainer unit jenis ekspansi langsung ini menggunakan alat ekspansi berupa pipa kapiler dan TXV jenis external equalizer. Untuk menentukan ukuran pipa kapiler pada pada trainer unit jenis ekspansi langsung menggunakan program aplikasi CapSel vesi 1,0. Dengan menggunakan data-data input jenis refrigeran R-134A, kapasitas refrigerasi 2..637,6 Watt (9000 BTU/jam), temperatur evaporasi 5 °C, temperatur kondensasi 47 °C, dan temperatur gas balik 12 °C, diperoleh data ukuran pipa kapiler yang disarankan yaitu panjang pipa kapiler 1,47 m dengan diameter dalam 2,50 mm.Pengujian dilakukan dengan memvariasi kecepatan udara yang keluar saluran udara pada posisi high speed (22,3 ft/s) dan pada low speed (7,9 ft/s). Data temperatur dan tekanan refrigeran diukur pada 4 titik pengukuran serta pengukuran arus listrik yang masuk ke sistem. Setelah dilakukan pengolahan data dan dimasukkan ke program aplikasi Coolpack, maka didapatkan COP dan EER rata-rata pada posisi low speed menghasilkan harga yang lebih besar dibandingkan pada posisi high speed.

Kata kunci

Jaringan kolaborasi para penulis

34 penulis · 115 tautan kepenulisan bersama · 6 lintas organisasi

Arahkan kursor atau ketuk sebuah nama untuk menyorot rekan penulisnya. Klik dua kali untuk membuka halaman penulis.

  • Politeknik Negeri Bali
  • Universitas Sains dan Teknologi Jayapura
  • Keio University
  • Afiliasi tidak diketahui
  • Organisasi berbeda
  • Organisasi sama
  • Afiliasi tidak diketahui
  • Garis lebih tebal = lebih banyak artikel bersama · lingkaran lebih besar = lebih banyak artikel
Tampilkan sebagai tabel
Rekan penulisOrganisasiArtikel bersama
I Nyoman SuamirPoliteknik Negeri Bali7
I Dewa Gede Agus Tri PutraPoliteknik Negeri Bali4
Ketut BangsePoliteknik Negeri Bali4
Putu Wijaya SunuPoliteknik Negeri Bali4
Adi WinartaPoliteknik Negeri Bali4
I Nengah ArditaPoliteknik Negeri Bali3
Achmad WiboloPoliteknik Negeri Bali2
Made Ery ArsanaPoliteknik Negeri Bali2
Daud Simon AnakottaparyPoliteknik Negeri Bali2
I Made RastaAfiliasi tidak diketahui2
I Nyoman SuamirAfiliasi tidak diketahui2
I Gusti Ketut PujaPoliteknik Negeri Bali2
Hendry Y. NanlohyUniversitas Sains dan Teknologi Jayapura1
Helen RiupassaUniversitas Sains dan Teknologi Jayapura1
Masaki YamaguchiKeio University1
. SudirmanAfiliasi tidak diketahui1
I Wayan SuastawaPoliteknik Negeri Bali1
I Nengah Darma SusilaPoliteknik Negeri Bali1
I Wayan TemajaPoliteknik Negeri Bali1
I Gede Artha NegaraPoliteknik Negeri Bali1
I B G WidiantaraPoliteknik Negeri Bali1
I Putu AstawaPoliteknik Negeri Bali1
I Ketut WidanaPoliteknik Negeri Bali1
Ni Wayan SumetriPoliteknik Negeri Bali1
I Putu Eka IdrayanaPoliteknik Negeri Bali1
Anak Agung Ngurah Dwi Indra PutraPoliteknik Negeri Bali1
Sudirman SudirmanPoliteknik Negeri Bali1
I Gusti Agung Bagus WirajatiPoliteknik Negeri Bali1
I Ketut SuparwikaPoliteknik Negeri Bali1
I Putu Sandi RadityaPoliteknik Negeri Bali1
I Wayan Adi SubagiaAfiliasi tidak diketahui1

Afiliasi berasal dari OpenAlex; metadata OAI-PMH jurnal tidak memuatnya. Penulis tanpa ID OpenAlex dicocokkan berdasarkan nama, sehingga dua orang bisa tergabung atau satu orang bisa terpisah.

Sumber metadata: OAI-PMH (metadata jurnal) https://ojs2.pnb.ac.id/index.php/JAMETECH/oai, pertama di-harvest 19 Nov 2026, terakhir terlihat 19 Nov 2026.
Metadata asli (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/  http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
	<dc:title xml:lang="en-US">Penentuan ukuran pipa kapiler dengan program aplikasi CapSel Versi 1.0 pada AC trainer unit jenis ekspansi langsung dengan R-410A</dc:title>
	<dc:title xml:lang="id-ID">Penentuan ukuran pipa kapiler dengan program aplikasi CapSel Versi 1.0 pada AC trainer unit jenis ekspansi langsung dengan R-410A</dc:title>
	<dc:creator>Susila, I Dewa Made</dc:creator>
	<dc:creator>Subagia, I Wayan Adi</dc:creator>
	<dc:creator>Rasta, I Made</dc:creator>
	<dc:subject xml:lang="en-US">Direct expansion type AC</dc:subject>
	<dc:subject xml:lang="en-US">capillary tube</dc:subject>
	<dc:subject xml:lang="en-US">R410a</dc:subject>
	<dc:subject xml:lang="en-US">performance</dc:subject>
	<dc:subject xml:lang="en-US">EER</dc:subject>
	<dc:subject xml:lang="id-ID">AC jenis ekspansi langsung</dc:subject>
	<dc:subject xml:lang="id-ID">pipa kapiler</dc:subject>
	<dc:subject xml:lang="id-ID">R410a</dc:subject>
	<dc:subject xml:lang="id-ID">performansi</dc:subject>
	<dc:subject xml:lang="id-ID">EER</dc:subject>
	<dc:description xml:lang="en-US">The use of air conditioning system currently mostly uses the vapor compression cycle. One such air conditioning machine is a direct expansion type AC. In this type of air conditioner, the air is directly cooled by the refrigerant. Cold air is flowed through the air duct to be entered into the room to be cooled. The refrigerant used is R-410A which does not contain chlorine so it does not cause depletion of the ozone layer because it has an ODP = 0. This direct expansion unit trainer uses an expansion device in the form of a capillary tube and an external equalizer type TXV. To determine the size of the capillary tube on the trainer unit, the direct expansion type uses the CapSel version 1.0 application program. By using the input data for refrigerant type R-134A, refrigeration capacity 2,637.6 Watt (9000 BTU/hour), evaporation temperature 5 °C condensation temperature 47 °C, and return gas temperature 12 °C, the recommended capillary pipe size data is obtained, namely the length of the pipe. capillary 1.47 m with an inner diameter of 2.50 mm. The test was carried out by varying the velocity of the air leaving the airways at high speed (22.3 ft/s) and at low speed (7.9 ft/s). The refrigerant temperature and pressure data are measured at 4 measurement points and the measurement of the electric current entering the system. After processing the data and entering it into the Coolpack application program, the average COP and EER in the low speed position produce a higher price than the high speed position.</dc:description>
	<dc:description xml:lang="id-ID">Penggunaan mesin pengkondisian udara saat ini paling banyak menggunakan siklus kompresi uap. Salah satu mesin pengkondisian udara tersebut adalah AC jenis ekspansi langsung. Pada AC jenis ini udara langsung didinginkan oleh refrigeran. Udara dingin dialirkan melalui saluran udara untuk dimasukan ke dalam ruangan yang akan didinginkan. Refrigeran yang digunakan adalah R-410A yang tidak mengandung unsur khlor sehingga tidak menyebabkan penipisan lapisan ozon karena mempunyai ODP = 0. Trainer unit jenis ekspansi langsung ini menggunakan alat ekspansi berupa pipa kapiler dan TXV jenis external equalizer. Untuk menentukan ukuran pipa kapiler pada pada trainer unit jenis ekspansi langsung menggunakan program aplikasi CapSel vesi 1,0. Dengan menggunakan data-data input jenis refrigeran R-134A, kapasitas refrigerasi 2..637,6 Watt (9000 BTU/jam), temperatur evaporasi 5 °C, temperatur kondensasi 47 °C, dan temperatur gas balik 12 °C, diperoleh data ukuran pipa kapiler yang disarankan yaitu panjang pipa kapiler 1,47 m dengan diameter dalam 2,50 mm.Pengujian dilakukan dengan memvariasi kecepatan udara yang keluar saluran udara pada posisi high speed (22,3 ft/s) dan pada low speed (7,9 ft/s). Data temperatur dan tekanan refrigeran diukur pada 4 titik pengukuran serta pengukuran arus listrik yang masuk ke sistem. Setelah dilakukan pengolahan data dan dimasukkan ke program aplikasi Coolpack, maka didapatkan COP dan EER rata-rata pada posisi low speed menghasilkan&amp;nbsp; harga yang lebih besar dibandingkan pada posisi high speed.</dc:description>
	<dc:publisher xml:lang="en-US">Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali</dc:publisher>
	<dc:date>2022-03-31</dc:date>
	<dc:type>info:eu-repo/semantics/article</dc:type>
	<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
	<dc:type xml:lang="en-US">Peer-reviewed Article</dc:type>
	<dc:format>application/pdf</dc:format>
	<dc:identifier>https://ojs2.pnb.ac.id/index.php/JAMETECH/article/view/441</dc:identifier>
	<dc:identifier>10.31940/jametech.v3i1.31-35</dc:identifier>
	<dc:source xml:lang="en-US"> Journal of Applied Mechanical Engineering and Green Technology; Vol. 3 No. 1 (2022): March 2022; 31-35</dc:source>
	<dc:source>2684-8201</dc:source>
	<dc:source>2655-9145</dc:source>
	<dc:source>10.31940/jametech.v3i1</dc:source>
	<dc:language>ind</dc:language>
	<dc:relation>https://ojs2.pnb.ac.id/index.php/JAMETECH/article/view/441/236</dc:relation>
	<dc:rights xml:lang="en-US">Copyright (c) 2022  Journal of Applied Mechanical Engineering and Green Technology</dc:rights>
	<dc:rights xml:lang="en-US">https://scholar.google.com/citations?hl=en&amp;view_op=list_works&amp;authuser=2&amp;gmla=AJsN-F5k01DNihBDbooUvlNxExv-WhpB3DyY0tjGvHKGcOovATy6tUweEZBP3T70BKOQ_1Vu8vDBsjKH91JWXJ8-wUV3JCO9xIjSPLsxXRi8L5d6dn6VJWk&amp;user=PhqmFRYAAAAJ</dc:rights>
</oai_dc:dc>