Simulasi penerapan looping system JTR untuk meningkatkan layanan pelanggan PT. PLN (Persero) menggunakan perangkat lunak ETAP

Journal of Applied Mechanical Engineering and Green Technology · Vol. 3 No. 2 (2022) · hlm. 78–86

DOI
10.31940/jametech.v3i2.78-86
ISSN
2684-8201, 2655-9145
Terbit
2022-07-31
Penerbit
Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali
Bahasa
ind

Abstrak

Inggris

In the process of implementing a looping low-voltage network. In this study, the author analyzes the application looping of low-voltage networks in premium bronze customers which is applied to the DB0575 and DB0292 substations. There are several things that are analyzed in this study, namely transformer loading, voltage drop, loading of KHA, analysis of the best networks, and protection of NH Fuse. This research uses software in simulating the application looping of low-voltage networks. Transformer loading before the application of looping low voltage networks on DB0575 and DB0292 are 28.2% and 48.95% while after the application of looping of low-voltage networks are 28.2% and 51.9%. The smallest value of voltage drop and loading of KHA are resulted in the 1st direction at the DB0575 substation with a value of 1.17% and 7.08% and the 4th direction at the DB0292 substation with a value of 0.73% and 17.91%, And the recommended protection rating for the DB0575 substation after the application is using the NH Fuse 'gG' rated current 200 A with a maximum voltage of 690 V and a rated breaking capacity of 50 kA as a protection system on low voltage distribution panel for a 3-phase 250 kVA 2-way distribution transformer. Meanwhile, the DB0292 substation uses an NH Fuse 'gG' rated current 125 A with a maximum voltage of 690 V and a rated breaking capacity of 50 kA as a protection system on low voltage distribution panel for a 3-phase 315 kVA 4-way distribution transformer.

Bahasa Indonesia

Dalam proses penerapan looping jaringan tegangan rendah terdapat beberapa standar yang harus dipenuhi. Pada kajian ini, penulis menganalisis penerapan looping jaringan tegangan rendah pada pelanggan premium bronze Klinik Braia yang diterapkan pada gardu DB0575 dan DB0292. Adapun beberapa hal yang dianalisis dalam penelitian ini yaitu Pembebanan transformator, drop tegangan, pembebanan KHA, analisis jurusan, dan proteksi NH Fuse. Penelitian ini menggunakan software ETAP 16.00 dalam simulasi penerapan looping jaringan tegangan rendah. Adapun hasil penelitian ini sebelum penerapan looping JTR pembebanan transformator pada DB0575 dan DB0292 berturut-turut 28,2% dan 48,95% sedangkan setelah penerapan looping JTR menjadi 28,2% dan 51,9%. Nilai drop tegangan dan pembebanan KHA yang terkecil berturut-turut dihasilkan pada jurusan 1 pada gardu DB0575 dengan nilai 1.17% dan 7.08% dan jurusan 4 pada gardu DB0292 dengan nilai 0.73% dan 17.91%. Dan rating proteksi yang direkomendasikan gardu DB0575 setelah penerapan menggunakan NH Fuse ‘gG’ rated current 200 A dengan tegangan maksimum 690 V dan rated breaking capacity 50 kA sebagai sistem proteksi pada PHB-TR untuk transformator distribusi 3 phasa 250 kVA 2 jurusan. Sedangkan untuk gardu DB0292 menggunakan NH Fuse ‘gG’ rated current 125 A dengan tegangan maksimum 690 V dan rated breaking capacity 50 kA sebagai sistem proteksi pada PHB-TR untuk transformator distribusi 3 phasa 315 kVA 4 jurusan.

Kata kunci

Jaringan kolaborasi para penulis

40 penulis · 137 tautan kepenulisan bersama · menampilkan 40 yang paling banyak terhubung

Arahkan kursor atau ketuk sebuah nama untuk menyorot rekan penulisnya. Klik dua kali untuk membuka halaman penulis.

  • Politeknik Negeri Bali
  • Afiliasi tidak diketahui
  • Organisasi berbeda
  • Organisasi sama
  • Afiliasi tidak diketahui
  • Garis lebih tebal = lebih banyak artikel bersama · lingkaran lebih besar = lebih banyak artikel
Tampilkan sebagai tabel
Rekan penulisOrganisasiArtikel bersama
I Gde Nyoman SangkaPoliteknik Negeri Bali3
I Nyoman MudianaPoliteknik Negeri Bali3
Ardy FirmanAfiliasi tidak diketahui3
I Ketut PartiPoliteknik Negeri Bali2
Anak Agung Ngurah Made NarottamaPoliteknik Negeri Bali2
I Nyoman SugiartaPoliteknik Negeri Bali2
I Wayan Raka ArdanaPoliteknik Negeri Bali2
I Wayan TeresnaPoliteknik Negeri Bali2
I G A M SunayaAfiliasi tidak diketahui2
Nyoman MudianaAfiliasi tidak diketahui2
I Made Sumerta YasaPoliteknik Negeri Bali2
I Wayan JondraPoliteknik Negeri Bali1
Ni Putu Indah Permata SariPoliteknik Negeri Bali1
I Gusti Ngurah Ade PujanaPoliteknik Negeri Bali1
I Putu Gede Giri SatriawanPoliteknik Negeri Bali1
I Made Eri SetiadiPoliteknik Negeri Bali1
I Putu Bagus Wisnu SaputraPoliteknik Negeri Bali1
Wayan Nara WisesaPoliteknik Negeri Bali1
Dewa Ayu Indah Cahya DewiPoliteknik Negeri Bali1
I Gede Suputra WidharmaPoliteknik Negeri Bali1
Kadek Amerta YasaPoliteknik Negeri Bali1
Ida Bagus Irawan PurnamaPoliteknik Negeri Bali1
I Gusti Putu Mastawan Eka PutraPoliteknik Negeri Bali1
I Kadek Angga Aditya PutraPoliteknik Negeri Bali1
I Dewa Gede Agung Raisa GiovaniPoliteknik Negeri Bali1
Muhammad Dzaky Abyan NaufalPoliteknik Negeri Bali1
Ni Kadek RahayuPoliteknik Negeri Bali1
IBK SugiriantaAfiliasi tidak diketahui1
Djoko SuhantonoPoliteknik Negeri Bali1
I Wayan SuwardanaPoliteknik Negeri Bali1
I Ayu Rai WulandariAfiliasi tidak diketahui1
Febry Setyacahyana PAfiliasi tidak diketahui1
I Wayan Suwardana SuwardanaAfiliasi tidak diketahui1
I Gde Wahyu Antara KurniawanAfiliasi tidak diketahui1
I Nyoman Gede Arya AstawaPoliteknik Negeri Bali1
Ni Kadek Dessy HariyantiPoliteknik Negeri Bali1

Afiliasi berasal dari OpenAlex; metadata OAI-PMH jurnal tidak memuatnya. Penulis tanpa ID OpenAlex dicocokkan berdasarkan nama, sehingga dua orang bisa tergabung atau satu orang bisa terpisah.

Sumber metadata: OAI-PMH (metadata jurnal) https://ojs2.pnb.ac.id/index.php/JAMETECH/oai, pertama di-harvest 19 Nov 2026, terakhir terlihat 19 Nov 2026.
Metadata asli (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/  http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
	<dc:title xml:lang="en-US">Simulasi penerapan looping system JTR untuk meningkatkan layanan pelanggan PT. PLN (Persero) menggunakan perangkat lunak ETAP</dc:title>
	<dc:title xml:lang="id-ID">Simulasi penerapan looping system JTR untuk meningkatkan layanan pelanggan PT. PLN (Persero) menggunakan perangkat lunak ETAP</dc:title>
	<dc:creator>Sutawinaya, I Putu</dc:creator>
	<dc:creator>Sudiartha, I Wayan</dc:creator>
	<dc:creator>Ta, I Ketut</dc:creator>
	<dc:creator>Saputra, I Gede Guntur</dc:creator>
	<dc:subject xml:lang="id-ID">Looping system JTR</dc:subject>
	<dc:subject xml:lang="id-ID">pelanggan premium</dc:subject>
	<dc:subject xml:lang="id-ID">drop tegangan</dc:subject>
	<dc:subject xml:lang="id-ID">pembebanan transformator</dc:subject>
	<dc:subject xml:lang="id-ID">KHA</dc:subject>
	<dc:subject xml:lang="id-ID">proteksi</dc:subject>
	<dc:subject xml:lang="id-ID">ETAP 16.0</dc:subject>
	<dc:subject xml:lang="en-US">Looping system JTR</dc:subject>
	<dc:subject xml:lang="en-US">premium customer</dc:subject>
	<dc:subject xml:lang="en-US">voltage drop</dc:subject>
	<dc:subject xml:lang="en-US">transformer loading</dc:subject>
	<dc:subject xml:lang="en-US">KHA</dc:subject>
	<dc:subject xml:lang="en-US">protection</dc:subject>
	<dc:subject xml:lang="en-US">ETAP 16.0</dc:subject>
	<dc:description xml:lang="en-US">In the process of implementing a looping low-voltage network. In this study, the author analyzes the application looping of low-voltage networks in premium bronze customers which is applied to the DB0575 and DB0292 substations. There are several things that are analyzed in this study, namely transformer loading, voltage drop, loading of KHA, analysis of the best networks, and protection of NH Fuse. This research uses software in simulating the application looping of low-voltage networks. Transformer loading before the application of looping low voltage networks on DB0575 and DB0292 are 28.2% and 48.95% while after the application of looping of low-voltage networks are 28.2% and 51.9%. The smallest value of voltage drop and loading of KHA are resulted in the 1st direction at the DB0575 substation with a value of 1.17% and 7.08% and the 4th direction at the DB0292 substation with a value of 0.73% and 17.91%,&amp;nbsp; And the recommended protection rating for the DB0575 substation after the application is using the NH Fuse 'gG' rated current 200 A with a maximum voltage of 690 V and a rated breaking capacity of 50 kA as a protection system on low voltage distribution panel for a 3-phase 250 kVA 2-way distribution transformer. Meanwhile, the DB0292 substation uses an NH Fuse 'gG' rated current 125 A with a maximum voltage of 690 V and a rated breaking capacity of 50 kA as a protection system on low voltage distribution panel for a 3-phase 315 kVA 4-way distribution transformer.</dc:description>
	<dc:description xml:lang="id-ID">Dalam proses penerapan looping jaringan tegangan rendah terdapat beberapa standar yang harus dipenuhi. Pada kajian ini, penulis menganalisis penerapan looping jaringan tegangan rendah pada pelanggan premium bronze Klinik Braia yang diterapkan pada gardu DB0575 dan DB0292. Adapun beberapa hal yang dianalisis dalam penelitian ini yaitu Pembebanan transformator, drop tegangan, pembebanan KHA, analisis jurusan, dan proteksi NH Fuse. Penelitian ini menggunakan software ETAP 16.00 dalam simulasi penerapan looping jaringan tegangan rendah. Adapun hasil penelitian ini sebelum penerapan looping JTR pembebanan transformator pada DB0575 dan DB0292 berturut-turut 28,2% dan 48,95% sedangkan setelah penerapan looping JTR menjadi 28,2% dan 51,9%. Nilai drop tegangan dan pembebanan KHA yang terkecil berturut-turut dihasilkan pada jurusan 1 pada gardu DB0575 dengan nilai 1.17% dan 7.08% dan jurusan 4 pada gardu DB0292 dengan nilai 0.73% dan 17.91%. Dan rating proteksi yang direkomendasikan gardu DB0575 setelah penerapan menggunakan NH Fuse ‘gG’ rated current 200 A dengan tegangan maksimum 690 V dan rated breaking capacity 50 kA sebagai sistem proteksi pada PHB-TR untuk transformator distribusi 3 phasa 250 kVA 2 jurusan. Sedangkan untuk gardu DB0292 menggunakan NH Fuse ‘gG’ rated current 125 A dengan tegangan maksimum 690 V dan rated breaking capacity 50 kA sebagai sistem proteksi pada PHB-TR untuk transformator distribusi 3 phasa 315 kVA 4 jurusan.</dc:description>
	<dc:publisher xml:lang="en-US">Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali</dc:publisher>
	<dc:date>2022-07-31</dc:date>
	<dc:type>info:eu-repo/semantics/article</dc:type>
	<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
	<dc:type xml:lang="en-US">Peer-reviewed Article</dc:type>
	<dc:format>application/pdf</dc:format>
	<dc:identifier>https://ojs2.pnb.ac.id/index.php/JAMETECH/article/view/675</dc:identifier>
	<dc:identifier>10.31940/jametech.v3i2.78-86</dc:identifier>
	<dc:source xml:lang="en-US"> Journal of Applied Mechanical Engineering and Green Technology; Vol. 3 No. 2 (2022): July 2022; 78-86</dc:source>
	<dc:source>2684-8201</dc:source>
	<dc:source>2655-9145</dc:source>
	<dc:source>10.31940/jametech.v3i2</dc:source>
	<dc:language>ind</dc:language>
	<dc:relation>https://ojs2.pnb.ac.id/index.php/JAMETECH/article/view/675/360</dc:relation>
	<dc:rights xml:lang="en-US">Copyright (c) 2022  Journal of Applied Mechanical Engineering and Green Technology</dc:rights>
	<dc:rights xml:lang="en-US">https://scholar.google.com/citations?hl=en&amp;view_op=list_works&amp;authuser=2&amp;gmla=AJsN-F5k01DNihBDbooUvlNxExv-WhpB3DyY0tjGvHKGcOovATy6tUweEZBP3T70BKOQ_1Vu8vDBsjKH91JWXJ8-wUV3JCO9xIjSPLsxXRi8L5d6dn6VJWk&amp;user=PhqmFRYAAAAJ</dc:rights>
</oai_dc:dc>