Analisis Kinerja dan Stabilitas Temperatur Cold Room Skala Kecil menggunakan Sistem Refrigerasi Kompresi Uap 1 PK dengan Refrigeran R-410A

Journal of Applied Mechanical Engineering and Green Technology · Vol. 4 No. 2 (2026) · hlm. 46–52

DOI
10.31940/jametech.v4i2.46-52
ISSN
2684-8201, 2655-9145
Terbit
2026-10-22
Penerbit
Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali
Bahasa
ind

Abstrak

Inggris

A cold room is a storage technology used to maintain the quality of horticultural products through temperature and humidity control. This study aims to analyze the performance and temperature stability of a small-scale cold room using a vapor compression refrigeration system equipped with a 1 HP compressor and R-410A refrigerant. The research employed an experimental method by conducting direct testing on a cold room prototype. Data were collected using temperature sensors placed at several measurement points to evaluate temperature distribution during the cooling process. The observed parameters included evaporator temperature, condenser temperature, refrigerant pressure, cooling time, electrical power consumption, and the actual and ideal Coefficient of Performance (COP). The experimental data were analyzed in the form of tables and graphs to determine temperature stability and refrigeration system performance. The experiments were conducted under two operating conditions, namely no-load and 100 kg load conditions. Temperature measurements were recorded using a four-channel data logger at 5-second intervals for 120 minutes. The analyzed parameters included pull-down time, temperature distribution, cooling load, and COP values. The results showed that the system was able to reach a temperature of 2°C within approximately ±30 minutes under no-load conditions and ±40 minutes under loaded conditions. The storage temperature could be maintained within the range of 2–8°C, with temperature variations between measurement points of approximately ±3°C. The total cooling load was 0.734 kW, with the largest contribution originating from the product load. The actual COP value of 3.455 was close to the ideal COP value of 3.476. These findings indicate that the small-scale cold room system has stable and efficient performance and strong potential to be implemented as an energy-efficient storage solution for small and medium-scale enterprises.

Bahasa Indonesia

A cold room is a storage technology used to maintain the quality of horticultural products through temperature and humidity control. This study aims to analyze the performance and temperature stability of a small-scale cold room using a vapor compression refrigeration system equipped with a 1 HP compressor and R-410A refrigerant. The research employed an experimental method by conducting direct testing on a cold room prototype. Data were collected using temperature sensors placed at several measurement points to evaluate temperature distribution during the cooling process. The observed parameters included evaporator temperature, condenser temperature, refrigerant pressure, cooling time, electrical power consumption, and the actual and ideal Coefficient of Performance (COP). The experimental data were analyzed in the form of tables and graphs to determine temperature stability and refrigeration system performance. The experiments were conducted under two operating conditions, namely no-load and 100 kg load conditions. Temperature measurements were recorded using a four-channel data logger at 5-second intervals for 120 minutes. The analyzed parameters included pull-down time, temperature distribution, cooling load, and COP values. The results showed that the system was able to reach a temperature of 2°C within approximately ±30 minutes under no-load conditions and ±40 minutes under loaded conditions. The storage temperature could be maintained within the range of 2–8°C, with temperature variations between measurement points of approximately ±3°C. The total cooling load was 0.734 kW, with the largest contribution originating from the product load. The actual COP value of 3.455 was close to the ideal COP value of 3.476. These findings indicate that the small-scale cold room system has stable and efficient performance and strong potential to be implemented as an energy-efficient storage solution for small and medium-scale enterprises.

Kata kunci

Jaringan kolaborasi para penulis

39 penulis · 111 tautan kepenulisan bersama

Arahkan kursor atau ketuk sebuah nama untuk menyorot rekan penulisnya. Klik dua kali untuk membuka halaman penulis.

  • Politeknik Negeri Bali
  • Afiliasi tidak diketahui
  • Organisasi berbeda
  • Organisasi sama
  • Afiliasi tidak diketahui
  • Garis lebih tebal = lebih banyak artikel bersama · lingkaran lebih besar = lebih banyak artikel
Tampilkan sebagai tabel
Rekan penulisOrganisasiArtikel bersama
I Wayan TemajaPoliteknik Negeri Bali4
I Kadek DwianaPoliteknik Negeri Bali3
I Nyoman Gede BaliartaPoliteknik Negeri Bali2
I Wayan Adi SubagiaPoliteknik Negeri Bali2
I Putu Merta AdnyanaPoliteknik Negeri Bali2
I Nengah Ludra AntaraPoliteknik Negeri Bali2
I Wayan Adi SubagiaPoliteknik Negeri Bali2
I Dewa Gede Agus Tri PutraPoliteknik Negeri Bali1
I B G WidiantaraPoliteknik Negeri Bali1
Ida Ayu Anom ArsaniPoliteknik Negeri Bali1
I Wayan SutinaPoliteknik Negeri Bali1
Komang Widhi WidanthaPoliteknik Negeri Bali1
Made Ery ArsanaPoliteknik Negeri Bali1
Arbyansyah DarmawanPoliteknik Negeri Bali1
Putu Wijaya SunuPoliteknik Negeri Bali1
I Dewa Made SusilaPoliteknik Negeri Bali1
I Nengah ArditaPoliteknik Negeri Bali1
I Dewa Gede Agus Tri PutraAfiliasi tidak diketahui1
Agustriputra IDGAfiliasi tidak diketahui1
I Wayan Agus Rantia DanaPoliteknik Negeri Bali1
I Made Bagus Panji AdityaPoliteknik Negeri Bali1
I Komang Risky Putra WibawaAfiliasi tidak diketahui1
I Made Prasana YogaPoliteknik Negeri Bali1
Ida Bagus Gde WidiantaraAfiliasi tidak diketahui1
Made Ery ArsanaAfiliasi tidak diketahui1
I Dewa Made Cipta SantosaAfiliasi tidak diketahui1
I Nyoman SutarnaPoliteknik Negeri Bali1
I Nyoman GunungPoliteknik Negeri Bali1
Ketut BangsePoliteknik Negeri Bali1
I Made Duta IrawanPoliteknik Negeri Bali1
I Made Angga AntaraPoliteknik Negeri Bali1
Nyoman SutarnaPoliteknik Negeri Bali1
Ida Bagus Gd WidiantaraAfiliasi tidak diketahui1
I Made Ery ArsanaPoliteknik Negeri Bali1

Afiliasi berasal dari OpenAlex; metadata OAI-PMH jurnal tidak memuatnya. Penulis tanpa ID OpenAlex dicocokkan berdasarkan nama, sehingga dua orang bisa tergabung atau satu orang bisa terpisah.

Sumber metadata: OAI-PMH (metadata jurnal) https://ojs2.pnb.ac.id/index.php/JAMETECH/oai, pertama di-harvest 19 Nov 2026, terakhir terlihat 19 Nov 2026.
Metadata asli (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/  http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
	<dc:title xml:lang="en-US">Analisis Kinerja dan Stabilitas Temperatur Cold Room Skala Kecil menggunakan Sistem Refrigerasi Kompresi Uap 1 PK dengan Refrigeran R-410A</dc:title>
	<dc:title xml:lang="id-ID">Analisis Kinerja dan Stabilitas Temperatur Cold Room Skala Kecil menggunakan Sistem Refrigerasi Kompresi Uap 1 PK dengan Refrigeran R-410A</dc:title>
	<dc:creator>Anakottapary, Daud Simon</dc:creator>
	<dc:creator>I Gede Artha Negara</dc:creator>
	<dc:creator>Luh Putu Ike Midiani</dc:creator>
	<dc:creator>Edo Kriswidianto</dc:creator>
	<dc:creator>I Wayan Temaja</dc:creator>
	<dc:subject xml:lang="id-ID">cold room</dc:subject>
	<dc:subject xml:lang="id-ID">COP</dc:subject>
	<dc:subject xml:lang="id-ID">temperature stability</dc:subject>
	<dc:subject xml:lang="id-ID">R-410A</dc:subject>
	<dc:subject xml:lang="id-ID">refrigeration</dc:subject>
	<dc:subject xml:lang="en-US">cold room</dc:subject>
	<dc:subject xml:lang="en-US">COP</dc:subject>
	<dc:subject xml:lang="en-US">temperature stability</dc:subject>
	<dc:subject xml:lang="en-US">R-410A</dc:subject>
	<dc:subject xml:lang="en-US">refrigeration</dc:subject>
	<dc:description xml:lang="en-US">A cold room is a storage technology used to maintain the quality of horticultural products through temperature and humidity control. This study aims to analyze the performance and temperature stability of a small-scale cold room using a vapor compression refrigeration system equipped with a 1 HP compressor and R-410A refrigerant. The research employed an experimental method by conducting direct testing on a cold room prototype. Data were collected using temperature sensors placed at several measurement points to evaluate temperature distribution during the cooling process. The observed parameters included evaporator temperature, condenser temperature, refrigerant pressure, cooling time, electrical power consumption, and the actual and ideal Coefficient of Performance (COP). The experimental data were analyzed in the form of tables and graphs to determine temperature stability and refrigeration system performance. The experiments were conducted under two operating conditions, namely no-load and 100 kg load conditions. Temperature measurements were recorded using a four-channel data logger at 5-second intervals for 120 minutes. The analyzed parameters included pull-down time, temperature distribution, cooling load, and COP values. The results showed that the system was able to reach a temperature of 2°C within approximately ±30 minutes under no-load conditions and ±40 minutes under loaded conditions. The storage temperature could be maintained within the range of 2–8°C, with temperature variations between measurement points of approximately ±3°C. The total cooling load was 0.734 kW, with the largest contribution originating from the product load. The actual COP value of 3.455 was close to the ideal COP value of 3.476. These findings indicate that the small-scale cold room system has stable and efficient performance and strong potential to be implemented as an energy-efficient storage solution for small and medium-scale enterprises.</dc:description>
	<dc:description xml:lang="id-ID">A cold room is a storage technology used to maintain the quality of horticultural products through temperature and humidity control. This study aims to analyze the performance and temperature stability of a small-scale cold room using a vapor compression refrigeration system equipped with a 1 HP compressor and R-410A refrigerant. The research employed an experimental method by conducting direct testing on a cold room prototype. Data were collected using temperature sensors placed at several measurement points to evaluate temperature distribution during the cooling process. The observed parameters included evaporator temperature, condenser temperature, refrigerant pressure, cooling time, electrical power consumption, and the actual and ideal Coefficient of Performance (COP). The experimental data were analyzed in the form of tables and graphs to determine temperature stability and refrigeration system performance. The experiments were conducted under two operating conditions, namely no-load and 100 kg load conditions. Temperature measurements were recorded using a four-channel data logger at 5-second intervals for 120 minutes. The analyzed parameters included pull-down time, temperature distribution, cooling load, and COP values. The results showed that the system was able to reach a temperature of 2°C within approximately ±30 minutes under no-load conditions and ±40 minutes under loaded conditions. The storage temperature could be maintained within the range of 2–8°C, with temperature variations between measurement points of approximately ±3°C. The total cooling load was 0.734 kW, with the largest contribution originating from the product load. The actual COP value of 3.455 was close to the ideal COP value of 3.476. These findings indicate that the small-scale cold room system has stable and efficient performance and strong potential to be implemented as an energy-efficient storage solution for small and medium-scale enterprises.</dc:description>
	<dc:publisher xml:lang="en-US">Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali</dc:publisher>
	<dc:date>2026-10-22</dc:date>
	<dc:type>info:eu-repo/semantics/article</dc:type>
	<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
	<dc:type xml:lang="en-US">Peer-reviewed Article</dc:type>
	<dc:format>application/pdf</dc:format>
	<dc:identifier>https://ojs2.pnb.ac.id/index.php/JAMETECH/article/view/3333</dc:identifier>
	<dc:identifier>10.31940/jametech.v4i2.46-52</dc:identifier>
	<dc:source xml:lang="en-US"> Journal of Applied Mechanical Engineering and Green Technology; Vol. 4 No. 2 (2026): Oktober; 46-52</dc:source>
	<dc:source>2684-8201</dc:source>
	<dc:source>2655-9145</dc:source>
	<dc:source>10.31940/jametech.v4i2</dc:source>
	<dc:language>ind</dc:language>
	<dc:relation>https://ojs2.pnb.ac.id/index.php/JAMETECH/article/view/3333/1593</dc:relation>
	<dc:rights xml:lang="en-US">Copyright (c) 2026  Journal of Applied Mechanical Engineering and Green Technology</dc:rights>
	<dc:rights xml:lang="en-US">https://scholar.google.com/citations?hl=en&amp;view_op=list_works&amp;authuser=2&amp;gmla=AJsN-F5k01DNihBDbooUvlNxExv-WhpB3DyY0tjGvHKGcOovATy6tUweEZBP3T70BKOQ_1Vu8vDBsjKH91JWXJ8-wUV3JCO9xIjSPLsxXRi8L5d6dn6VJWk&amp;user=PhqmFRYAAAAJ</dc:rights>
</oai_dc:dc>