Kajian Unjuk Kerja Mesin Es dengan Variasi Panjang Pipa Kapiler dan Evaporator Plat Horisontal

Journal of Applied Mechanical Engineering and Green Technology · Vol. 4 No. 2 (2026) · hlm. 59–64

DOI
10.31940/jametech.v4i2.59-64
ISSN
2684-8201, 2655-9145
Terbit
2026-10-22
Penerbit
Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali
Bahasa
ind

Abstrak

Inggris

The thermal performance of a cube-ice machine is strongly governed by heat removal from the mould and the characteristics of the expansion device. This study evaluates an R22 vapour-compression ice machine equipped with a horizontal aluminium plate evaporator attached to a 12 × 18 cavity mould. Three nominal 0.73-mm-diameter capillary tubes with lengths of 0.656, 0.830, and 0.984 m were tested at measured high- and low-side pressures of 105 and 9 psi, respectively. Temperatures at four locations, compressor current, and the evaporator-to-mould thermal response were recorded, while cycle enthalpy parameters and COP were analysed using CoolPack. The 0.984 m capillary produced the lowest mean T4 temperature of −19.79 °C and a minimum of −21.1 °C, although the reported cycle COP and cooling capacity decreased to 4.98 and 151.12 W. In contrast, the 0.656 m capillary achieved the highest COP of 5.92 and a reported cooling capacity of 173.90 W, with a mean T4 temperature of −15.20 °C. During the mould test, the evaporator reached −21.0 °C, whereas the mould reached only −1.5 °C and maintained a mean temperature difference of 19.74 °C relative to the evaporator. The results reveal a trade-off between evaporator temperature reduction and cycle efficiency; non-uniform ice formation was primarily limited by evaporator-mould thermal contact and enclosure insulation.

Bahasa Indonesia

The thermal performance of a cube-ice machine is strongly governed by heat removal from the mould and the characteristics of the expansion device. This study evaluates an R22 vapour-compression ice machine equipped with a horizontal aluminium plate evaporator attached to a 12 × 18 cavity mould. Three nominal 0.73-mm-diameter capillary tubes with lengths of 0.656, 0.830, and 0.984 m were tested at measured high- and low-side pressures of 105 and 9 psi, respectively. Temperatures at four locations, compressor current, and the evaporator-to-mould thermal response were recorded, while cycle enthalpy parameters and COP were analysed using CoolPack. The 0.984 m capillary produced the lowest mean T4 temperature of −19.79 °C and a minimum of −21.1 °C, although the reported cycle COP and cooling capacity decreased to 4.98 and 151.12 W. In contrast, the 0.656 m capillary achieved the highest COP of 5.92 and a reported cooling capacity of 173.90 W, with a mean T4 temperature of −15.20 °C. During the mould test, the evaporator reached −21.0 °C, whereas the mould reached only −1.5 °C and maintained a mean temperature difference of 19.74 °C relative to the evaporator. The results reveal a trade-off between evaporator temperature reduction and cycle efficiency; non-uniform ice formation was primarily limited by evaporator-mould thermal contact and enclosure insulation.

Kata kunci

Jaringan kolaborasi para penulis

24 penulis · 80 tautan kepenulisan bersama · 3 lintas organisasi

Arahkan kursor atau ketuk sebuah nama untuk menyorot rekan penulisnya. Klik dua kali untuk membuka halaman penulis.

  • Politeknik Negeri Bali
  • Universitas Islam Negeri Maulana Malik Ibrahim
  • Afiliasi tidak diketahui
  • Organisasi berbeda
  • Organisasi sama
  • Afiliasi tidak diketahui
  • Garis lebih tebal = lebih banyak artikel bersama · lingkaran lebih besar = lebih banyak artikel
Tampilkan sebagai tabel
Rekan penulisOrganisasiArtikel bersama
I Wayan TemajaPoliteknik Negeri Bali3
I Dewa Gede Agus Tri PutraPoliteknik Negeri Bali3
Putu Wijaya SunuPoliteknik Negeri Bali2
Ida Ayu Anom ArsaniPoliteknik Negeri Bali2
I Wayan SutinaPoliteknik Negeri Bali2
Komang Widhi WidanthaPoliteknik Negeri Bali2
I Wayan Adi SubagiaPoliteknik Negeri Bali1
I B G WidiantaraPoliteknik Negeri Bali1
I Made SuartaPoliteknik Negeri Bali1
Sudirman SudirmanUniversitas Islam Negeri Maulana Malik Ibrahim1
Made SuartaPoliteknik Negeri Bali1
Made Ery ArsanaPoliteknik Negeri Bali1
. SudirmanAfiliasi tidak diketahui1
Achmad WiboloPoliteknik Negeri Bali1
I Ketut SuhermanPoliteknik Negeri Bali1
Luh Putu Ike MidianiPoliteknik Negeri Bali1
Daud Simon AnakottaparyPoliteknik Negeri Bali1
Edo KriswidiantoAfiliasi tidak diketahui1
I Wayan TemajaAfiliasi tidak diketahui1
Nyoman SugiarthaPoliteknik Negeri Bali1
I Wayan TemajaPoliteknik Negeri Bali1

Afiliasi berasal dari OpenAlex; metadata OAI-PMH jurnal tidak memuatnya. Penulis tanpa ID OpenAlex dicocokkan berdasarkan nama, sehingga dua orang bisa tergabung atau satu orang bisa terpisah.

Sumber metadata: OAI-PMH (metadata jurnal) https://ojs2.pnb.ac.id/index.php/JAMETECH/oai, pertama di-harvest 19 Nov 2026, terakhir terlihat 19 Nov 2026.
Metadata asli (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/  http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
	<dc:title xml:lang="en-US">Kajian Unjuk Kerja Mesin Es dengan Variasi Panjang Pipa Kapiler dan Evaporator Plat Horisontal</dc:title>
	<dc:title xml:lang="id-ID">Kajian Unjuk Kerja Mesin Es dengan Variasi Panjang Pipa Kapiler dan Evaporator Plat Horisontal</dc:title>
	<dc:creator>IDG, Agustriputra</dc:creator>
	<dc:creator>I Nyoman Gede Baliarta</dc:creator>
	<dc:creator>I Gede Artha Negara</dc:creator>
	<dc:subject xml:lang="id-ID">plate evaporator</dc:subject>
	<dc:subject xml:lang="id-ID">cube-ice machine</dc:subject>
	<dc:subject xml:lang="id-ID">capillary tube</dc:subject>
	<dc:subject xml:lang="id-ID">coefficient of performance</dc:subject>
	<dc:subject xml:lang="id-ID">ice formation</dc:subject>
	<dc:subject xml:lang="en-US">plate evaporator</dc:subject>
	<dc:subject xml:lang="en-US">cube-ice machine</dc:subject>
	<dc:subject xml:lang="en-US">capillary tube</dc:subject>
	<dc:subject xml:lang="en-US">coefficient of performance</dc:subject>
	<dc:subject xml:lang="en-US">ice formation</dc:subject>
	<dc:description xml:lang="en-US">The thermal performance of a cube-ice machine is strongly governed by heat removal from the mould and the characteristics of the expansion device. This study evaluates an R22 vapour-compression ice machine equipped with a horizontal aluminium plate evaporator attached to a 12 × 18 cavity mould. Three nominal 0.73-mm-diameter capillary tubes with lengths of 0.656, 0.830, and 0.984 m were tested at measured high- and low-side pressures of 105 and 9 psi, respectively. Temperatures at four locations, compressor current, and the evaporator-to-mould thermal response were recorded, while cycle enthalpy parameters and COP were analysed using CoolPack. The 0.984 m capillary produced the lowest mean T4 temperature of −19.79 °C and a minimum of −21.1 °C, although the reported cycle COP and cooling capacity decreased to 4.98 and 151.12 W. In contrast, the 0.656 m capillary achieved the highest COP of 5.92 and a reported cooling capacity of 173.90 W, with a mean T4 temperature of −15.20 °C. During the mould test, the evaporator reached −21.0 °C, whereas the mould reached only −1.5 °C and maintained a mean temperature difference of 19.74 °C relative to the evaporator. The results reveal a trade-off between evaporator temperature reduction and cycle efficiency; non-uniform ice formation was primarily limited by evaporator-mould thermal contact and enclosure insulation.</dc:description>
	<dc:description xml:lang="id-ID">The thermal performance of a cube-ice machine is strongly governed by heat removal from the mould and the characteristics of the expansion device. This study evaluates an R22 vapour-compression ice machine equipped with a horizontal aluminium plate evaporator attached to a 12 × 18 cavity mould. Three nominal 0.73-mm-diameter capillary tubes with lengths of 0.656, 0.830, and 0.984 m were tested at measured high- and low-side pressures of 105 and 9 psi, respectively. Temperatures at four locations, compressor current, and the evaporator-to-mould thermal response were recorded, while cycle enthalpy parameters and COP were analysed using CoolPack. The 0.984 m capillary produced the lowest mean T4 temperature of −19.79 °C and a minimum of −21.1 °C, although the reported cycle COP and cooling capacity decreased to 4.98 and 151.12 W. In contrast, the 0.656 m capillary achieved the highest COP of 5.92 and a reported cooling capacity of 173.90 W, with a mean T4 temperature of −15.20 °C. During the mould test, the evaporator reached −21.0 °C, whereas the mould reached only −1.5 °C and maintained a mean temperature difference of 19.74 °C relative to the evaporator. The results reveal a trade-off between evaporator temperature reduction and cycle efficiency; non-uniform ice formation was primarily limited by evaporator-mould thermal contact and enclosure insulation.</dc:description>
	<dc:publisher xml:lang="en-US">Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali</dc:publisher>
	<dc:date>2026-10-22</dc:date>
	<dc:type>info:eu-repo/semantics/article</dc:type>
	<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
	<dc:type xml:lang="en-US">Peer-reviewed Article</dc:type>
	<dc:format>application/pdf</dc:format>
	<dc:identifier>https://ojs2.pnb.ac.id/index.php/JAMETECH/article/view/3413</dc:identifier>
	<dc:identifier>10.31940/jametech.v4i2.59-64</dc:identifier>
	<dc:source xml:lang="en-US"> Journal of Applied Mechanical Engineering and Green Technology; Vol. 4 No. 2 (2026): Oktober; 59-64</dc:source>
	<dc:source>2684-8201</dc:source>
	<dc:source>2655-9145</dc:source>
	<dc:source>10.31940/jametech.v4i2</dc:source>
	<dc:language>ind</dc:language>
	<dc:relation>https://ojs2.pnb.ac.id/index.php/JAMETECH/article/view/3413/1597</dc:relation>
	<dc:rights xml:lang="en-US">Copyright (c) 2026  Journal of Applied Mechanical Engineering and Green Technology</dc:rights>
	<dc:rights xml:lang="en-US">https://scholar.google.com/citations?hl=en&amp;view_op=list_works&amp;authuser=2&amp;gmla=AJsN-F5k01DNihBDbooUvlNxExv-WhpB3DyY0tjGvHKGcOovATy6tUweEZBP3T70BKOQ_1Vu8vDBsjKH91JWXJ8-wUV3JCO9xIjSPLsxXRi8L5d6dn6VJWk&amp;user=PhqmFRYAAAAJ</dc:rights>
</oai_dc:dc>