Thermal Performance Evaluation of the Variation of Condenser Dimensions for Foodstuffs Transportation Cooling Systems

Logic: Jurnal Rancang Bangun dan Teknologi · Vol. 21 No. 3 (2021) · hlm. 184–189

DOI
10.31940/logic.v21i3.184-189
ISSN
2580-5649, 1412-114X
Terbit
2021-11-30
Penerbit
Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali
Bahasa
eng

Abstrak

The process of sending food using transportation requires a refrigeration system to keep the product fresh. Unsuitable temperatures will cause the transported products to often experience damage so that they are rejected in the mark. To achieve this, it is done through testing using a condenser with several variations of dimensions for a room temperature of 5oC. The dimensions of condenser-1 are (W 23 x H 14) inch2 x 19 mm, condenser-2 is (W 23 x H 14) inch2 x 26 mm, and condenser-3 is (W 23 x H 14) inch2 x 44 mm. The test results show that condenser-3 produces a faster cooling time compared to condenser-2 and condenser-1. Cooling time for condenser-3 is 1160 minutes, while condenser-2 and condenser-1 are 1560 minutes and 1860 minutes, respectively. Condenser-3 provides the lowest compression work of 42.131 kJ/kg compared to condensers 2 and 1, respectively 42.931 kJ/kg, and 46.147 kJ/kg. This has an impact on the COP value, namely condenser-3, condenser-2, and condenser-1 each of 3.437, 3.233, and 2.845. COP at condenser-3 occurs the highest. These results indicate that the largest condenser dimension gives the most optimum thermal performance results. An efficient refrigeration system has low compression work and high COP.

Kata kunci

Jaringan kolaborasi para penulis

11 penulis · 13 tautan kepenulisan bersama · 1 lintas organisasi

Arahkan kursor atau ketuk sebuah nama untuk menyorot rekan penulisnya. Klik dua kali untuk membuka halaman penulis.

  • University of Mataram
  • Politeknik Negeri Bali
  • Afiliasi tidak diketahui
  • Organisasi berbeda
  • Organisasi sama
  • Afiliasi tidak diketahui
  • Garis lebih tebal = lebih banyak artikel bersama · lingkaran lebih besar = lebih banyak artikel
Tampilkan sebagai tabel
Rekan penulisOrganisasiArtikel bersama
I Made SuartikaUniversity of Mataram2
Anak Agung Alit TriadiUniversity of Mataram1
Wisnu KawirianUniversity of Mataram1
I Ketut Perdana PutraUniversity of Mataram1
I Nyoman BudiartanaPoliteknik Negeri Bali1
Gilang Ade PutraUniversity of Mataram1
I Made Agus PutrawanPoliteknik Negeri Bali1
Ketut AdiPoliteknik Negeri Bali1
Gede Bawa SusanaAfiliasi tidak diketahui1

Afiliasi berasal dari OpenAlex; metadata OAI-PMH jurnal tidak memuatnya. Penulis tanpa ID OpenAlex dicocokkan berdasarkan nama, sehingga dua orang bisa tergabung atau satu orang bisa terpisah.

Sumber metadata: OAI-PMH (metadata jurnal) https://ojs2.pnb.ac.id/index.php/LOGIC/oai, pertama di-harvest 19 Nov 2026, terakhir terlihat 19 Nov 2026.
Metadata asli (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/  http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
	<dc:title xml:lang="en-US">Thermal Performance Evaluation of the Variation of Condenser Dimensions for Foodstuffs Transportation Cooling Systems</dc:title>
	<dc:creator>I Gede Bawa Susana</dc:creator>
	<dc:creator>I Gede Santosa</dc:creator>
	<dc:subject xml:lang="en-US">condenser</dc:subject>
	<dc:subject xml:lang="en-US">thermal performance</dc:subject>
	<dc:subject xml:lang="en-US">refrigeration system</dc:subject>
	<dc:subject xml:lang="en-US">coefficient of performance</dc:subject>
	<dc:description xml:lang="en-US">The process of sending food using transportation requires a refrigeration system to keep the product fresh. &amp;nbsp;Unsuitable temperatures will cause the transported products to often experience damage so that they are rejected in the mark.
To achieve this, it is done through testing using a condenser with several variations of dimensions for a room temperature of 5oC. The dimensions of condenser-1 are (W 23 x H 14) inch2 x 19 mm, condenser-2 is (W 23 x H 14) inch2 x 26 mm, and condenser-3 is (W 23 x H 14) inch2 x 44 mm. The test results show that condenser-3 produces a faster cooling time compared to condenser-2 and condenser-1. Cooling time for condenser-3 is 1160 minutes, while condenser-2 and condenser-1 are 1560 minutes and 1860 minutes, respectively.&amp;nbsp;Condenser-3 provides the lowest compression work of 42.131 kJ/kg compared to condensers 2 and 1, respectively 42.931 kJ/kg, and 46.147 kJ/kg. This has an impact on the COP value, namely condenser-3, condenser-2, and condenser-1 each of 3.437, 3.233, and 2.845. COP at condenser-3 occurs the highest. These results indicate that the largest condenser dimension gives the most optimum thermal performance results. An efficient refrigeration system has low compression work and high COP.</dc:description>
	<dc:publisher xml:lang="en-US">Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali</dc:publisher>
	<dc:date>2021-11-30</dc:date>
	<dc:type>info:eu-repo/semantics/article</dc:type>
	<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
	<dc:format>application/pdf</dc:format>
	<dc:identifier>https://ojs2.pnb.ac.id/index.php/LOGIC/article/view/94</dc:identifier>
	<dc:identifier>10.31940/logic.v21i3.184-189</dc:identifier>
	<dc:source xml:lang="en-US"> Logic : Jurnal Rancang Bangun dan Teknologi; Vol. 21 No. 3 (2021): November; 184-189</dc:source>
	<dc:source>2580-5649</dc:source>
	<dc:source>1412-114X</dc:source>
	<dc:source>10.31940/logic.v21i3</dc:source>
	<dc:language>eng</dc:language>
	<dc:relation>https://ojs2.pnb.ac.id/index.php/LOGIC/article/view/94/44</dc:relation>
	<dc:rights xml:lang="en-US">Copyright (c) 2021  Logic : Jurnal Rancang Bangun dan Teknologi</dc:rights>
	<dc:rights xml:lang="en-US">https://scholar.google.co.id/citations?user=smBuD3gAAAAJ&amp;hl=id</dc:rights>
</oai_dc:dc>