Ground Fault Protection Using Open Break Delta Grounding Transformer in Ungrounded System

Logic: Jurnal Rancang Bangun dan Teknologi · Vol. 19 No. 1 (2019) · hlm. 34–40

DOI
10.31940/logic.v19i1.1275
ISSN
2580-5649, 1412-114X
Terbit
2019-03-30
Penerbit
Pusat Penelitian dan Pengabdian kepada Masyarakat (P3M) Politeknik Negeri Bali
Bahasa
eng

Abstrak

One of the most common and difficult problems to solve in distribution power systems is the location and elimination of the ground fault. For the study of an electrical distribution network in ungrounded system operating at 20 kV on the primary and 380 V on the secondary. The model uses smaller nominal voltages consisting of 380 V on the primary and the secondary. The Ground fault protection system scheme uses over voltage relays and open break delta transformers, whereas for fault location detection using voltage transformers in star star connections.The highest single line to ground fault value is used for consideration of ballast rating selection. The single line to lowest ground fault value is used for setting the threshold on the voltage relay (59N). Referring to the result of the calculation of the highest single phase to ground voltage at point 1 is 144∠1800 volts, and the lowest point at 4 is 132∠1800 volts. A 200 ohm ballast impedance with 150 watts of power capacity, and an overvoltage threshold setting of 120 volts with TDS of 40. One phase fault protection mechanism works well at each point of interference, and voltage transformers are protected from overheating and damage.

Jaringan kolaborasi para penulis

3 penulis · 3 tautan kepenulisan bersama

Arahkan kursor atau ketuk sebuah nama untuk menyorot rekan penulisnya. Klik dua kali untuk membuka halaman penulis.

  • Politeknik Negeri Bandung
  • Organisasi berbeda
  • Organisasi sama
  • Afiliasi tidak diketahui
  • Garis lebih tebal = lebih banyak artikel bersama · lingkaran lebih besar = lebih banyak artikel
Tampilkan sebagai tabel
Rekan penulisOrganisasiArtikel bersama

Afiliasi berasal dari OpenAlex; metadata OAI-PMH jurnal tidak memuatnya. Penulis tanpa ID OpenAlex dicocokkan berdasarkan nama, sehingga dua orang bisa tergabung atau satu orang bisa terpisah.

Sumber metadata: OAI-PMH (metadata jurnal) https://ojs.pnb.ac.id/index.php/LOGIC/oai, pertama di-harvest 19 Nov 2026, terakhir terlihat 19 Nov 2026.
Metadata asli (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/  http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
	<dc:title xml:lang="en-US">Ground Fault Protection Using Open Break Delta Grounding Transformer in Ungrounded System</dc:title>
	<dc:creator>Suhono, Supriyanto</dc:creator>
	<dc:creator>Purnama, Hari</dc:creator>
	<dc:creator>Budi Utomo, Heri</dc:creator>
	<dc:description xml:lang="en-US">One of the most common and difficult problems to solve in distribution power systems is the location and elimination of the ground fault. For the study of an electrical distribution network in ungrounded system operating at 20 kV on the primary and 380 V on the secondary. The model uses smaller nominal voltages consisting of 380 V on the primary and the secondary. The Ground fault protection system scheme uses over voltage relays and open break delta transformers, whereas for fault location detection using voltage transformers in&amp;nbsp;star star connections.The highest single line to ground fault value is used for consideration of ballast rating selection. The single line to lowest ground fault value is used for setting the threshold on the voltage relay (59N). &amp;nbsp;Referring to the result of the calculation of the highest single phase to ground voltage at point 1 is 144∠1800 volts, and the lowest point at 4 is 132∠1800 volts. A 200 ohm ballast impedance with 150 watts of power capacity, and an overvoltage threshold setting of 120 volts with TDS of 40. One phase fault protection mechanism works well at each point of interference, and voltage transformers are protected from overheating and damage.</dc:description>
	<dc:publisher xml:lang="en-US">Pusat Penelitian dan Pengabdian kepada Masyarakat (P3M) Politeknik Negeri Bali</dc:publisher>
	<dc:date>2019-03-30</dc:date>
	<dc:type>info:eu-repo/semantics/article</dc:type>
	<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
	<dc:type xml:lang="en-US">Peer-reviewed Article</dc:type>
	<dc:format>application/pdf</dc:format>
	<dc:identifier>https://ojs.pnb.ac.id/index.php/LOGIC/article/view/1275</dc:identifier>
	<dc:identifier>10.31940/logic.v19i1.1275</dc:identifier>
	<dc:source xml:lang="en-US">Logic : Jurnal Rancang Bangun dan Teknologi; Vol 19 No 1 (2019): March; 34-40</dc:source>
	<dc:source>2580-5649</dc:source>
	<dc:source>1412-114X</dc:source>
	<dc:source>10.31940/logic.v19i1</dc:source>
	<dc:language>eng</dc:language>
	<dc:relation>https://ojs.pnb.ac.id/index.php/LOGIC/article/view/1275/986</dc:relation>
	<dc:rights xml:lang="en-US">Copyright (c) 2019 Logic : Jurnal Rancang Bangun dan Teknologi</dc:rights>
</oai_dc:dc>