Jurnal
SINTA 3
The grounding resistance improvement of distribution substation using multiple rods and wood charcoal as soil treatment
Matrix: Jurnal Manajemen Teknologi dan Informatika · Vol. 13 No. 1 (2023) · hlm. 33–41
ISSN 2580-5630, 2088-284X
Terbit 2023-03-30
Penerbit Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali
Bahasa eng
Abstrak
The grounding system plays the important role in securing the electric power system. Low grounding resistance ensures the proper operation of the grounding system. The lower the grounding resistance value, the easier current flow through the earth without any obstacles then prevents equipment from being damaged or causing the injury of personnel. According to the PUIL 2000 standard, grounding resistance should be less than 5Ω. Methods that can be performed to reduce grounding resistance are increasing the length and diameter of the grounding rod, using multiple rods, and treating the soil to reduce its resistivity. In this study, we would like to improve the grounding system of the KA2317 distribution substation located at Mertasari, Jimbaran in South Kuta, Bali which has a grounding resistance of 8.1Ω (more than 5Ω). The method that was applied in this study was grounding improvement by adding an electrode rod and adding wood charcoal to reduce soil resistivity. At the end of the study, grounding resistance can be reduced from 8.1Ω to 1.9 Ω or improved by 76.6%.
Jaringan kolaborasi para penulis
5 penulis ·
5 tautan kepenulisan bersama
Arahkan kursor atau ketuk sebuah nama untuk menyorot rekan penulisnya. Klik dua kali untuk membuka halaman penulis.
Organisasi berbeda
Organisasi sama
Afiliasi tidak diketahui
Garis lebih tebal = lebih banyak artikel bersama · lingkaran lebih besar = lebih banyak artikel
Tampilkan sebagai tabel
Afiliasi berasal dari OpenAlex; metadata OAI-PMH jurnal tidak memuatnya. Penulis tanpa ID OpenAlex dicocokkan berdasarkan nama, sehingga dua orang bisa tergabung atau satu orang bisa terpisah.
Sumber metadata: OAI-PMH (metadata jurnal) https://ojs2.pnb.ac.id/index.php/MATRIX/oai, pertama di-harvest 19 Nov 2026, terakhir terlihat 19 Nov 2026.
Metadata asli (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/ http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
<dc:title xml:lang="en-US">The grounding resistance improvement of distribution substation using multiple rods and wood charcoal as soil treatment</dc:title>
<dc:creator>Karmiathi, Ni Made</dc:creator>
<dc:creator>Puja Yoga, Putu Martin </dc:creator>
<dc:subject xml:lang="en-US">charcoal</dc:subject>
<dc:subject xml:lang="en-US">electrode rod</dc:subject>
<dc:subject xml:lang="en-US">grounding resistance</dc:subject>
<dc:description xml:lang="en-US">The grounding system plays the important role in securing the electric power system. Low grounding resistance ensures the proper operation of the grounding system. The lower the grounding resistance value, the easier current flow through the earth without any obstacles then prevents equipment from being damaged or causing the injury of personnel. According to the PUIL 2000 standard, grounding resistance should be less than 5Ω. Methods that can be performed to reduce grounding resistance are increasing the length and diameter of the grounding rod, using multiple rods, and treating the soil to reduce its resistivity. In this study, we would like to improve the grounding system of the KA2317 distribution substation located at Mertasari, Jimbaran in South Kuta, Bali which has a grounding resistance of 8.1Ω (more than 5Ω). The method that was applied in this study was grounding improvement by adding an electrode rod and adding wood charcoal to reduce soil resistivity. At the end of the study, grounding resistance can be reduced from 8.1Ω to 1.9 Ω or improved by 76.6%.</dc:description>
<dc:publisher xml:lang="en-US">Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali</dc:publisher>
<dc:date>2023-03-30</dc:date>
<dc:type>info:eu-repo/semantics/article</dc:type>
<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
<dc:type xml:lang="en-US">Peer-reviewed Article</dc:type>
<dc:format>application/pdf</dc:format>
<dc:identifier>https://ojs2.pnb.ac.id/index.php/MATRIX/article/view/963</dc:identifier>
<dc:identifier>10.31940/matrix.v13i1.33-41</dc:identifier>
<dc:source xml:lang="en-US">Matrix : Jurnal Manajemen Teknologi dan Informatika; Vol. 13 No. 1 (2023): Matrix: Jurnal Manajemen Teknologi dan Informatika; 33-41</dc:source>
<dc:source>2580-5630</dc:source>
<dc:source>2088-284X</dc:source>
<dc:source>10.31940/matrix.v13i1</dc:source>
<dc:language>eng</dc:language>
<dc:relation>https://ojs2.pnb.ac.id/index.php/MATRIX/article/view/963/515</dc:relation>
<dc:rights xml:lang="en-US">Copyright (c) 2023 Matrix : Jurnal Manajemen Teknologi dan Informatika</dc:rights>
<dc:rights xml:lang="en-US">https://scholar.google.co.id/citations?user=NDE5gXYAAAAJ&hl=id</dc:rights>
</oai_dc:dc>
Sitasi dan pengindeksan
Jumlah menurut tiap indeks pada 19 Nov 2026; setiap indeks menghitung sitasi dengan cara berbeda.
OpenAlex juga mencatat karya ini di: crossref, doaj.
Sitasi artikel ini
APA 7
Karmiathi, N. M., & Puja Yoga, P. M. (2023). The grounding resistance improvement of distribution substation using multiple rods and wood charcoal as soil treatment. Matrix: Jurnal Manajemen Teknologi dan Informatika, 13(1), 33–41. https://doi.org/10.31940/matrix.v13i1.33-41
Salin
IEEE
N. M. Karmiathi and P. M. Puja Yoga, “The grounding resistance improvement of distribution substation using multiple rods and wood charcoal as soil treatment,” Matrix: Jurnal Manajemen Teknologi dan Informatika, vol. 13, no. 1, pp. 33–41, 2023, doi: 10.31940/matrix.v13i1.33-41.
Salin
Dibuat dari metadata jurnal; periksa nama penulis sebelum dipakai.