Melola Discovery

← Melola Discovery

Jurnal SINTA 3

The grounding resistance improvement of distribution substation using multiple rods and wood charcoal as soil treatment

Matrix: Jurnal Manajemen Teknologi dan Informatika · Vol. 13 No. 1 (2023) · hlm. 33–41

DOI
10.31940/matrix.v13i1.33-41
ISSN
2580-5630, 2088-284X
Terbit
2023-03-30
Penerbit
Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali
Bahasa
eng

Abstrak

The grounding system plays the important role in securing the electric power system. Low grounding resistance ensures the proper operation of the grounding system. The lower the grounding resistance value, the easier current flow through the earth without any obstacles then prevents equipment from being damaged or causing the injury of personnel. According to the PUIL 2000 standard, grounding resistance should be less than 5Ω. Methods that can be performed to reduce grounding resistance are increasing the length and diameter of the grounding rod, using multiple rods, and treating the soil to reduce its resistivity. In this study, we would like to improve the grounding system of the KA2317 distribution substation located at Mertasari, Jimbaran in South Kuta, Bali which has a grounding resistance of 8.1Ω (more than 5Ω). The method that was applied in this study was grounding improvement by adding an electrode rod and adding wood charcoal to reduce soil resistivity. At the end of the study, grounding resistance can be reduced from 8.1Ω to 1.9 Ω or improved by 76.6%.

Kata kunci

Jaringan kolaborasi para penulis

5 penulis · 5 tautan kepenulisan bersama

Arahkan kursor atau ketuk sebuah nama untuk menyorot rekan penulisnya. Klik dua kali untuk membuka halaman penulis.

  • Politeknik Negeri Bali
  • Organisasi berbeda
  • Organisasi sama
  • Afiliasi tidak diketahui
  • Garis lebih tebal = lebih banyak artikel bersama · lingkaran lebih besar = lebih banyak artikel
Tampilkan sebagai tabel
Rekan penulisOrganisasiArtikel bersama
Ni Wayan WisswaniPoliteknik Negeri Bali2
I Kadek Adiana PutraPoliteknik Negeri Bali1
I Gusti Putu Mastawan Eka PutraPoliteknik Negeri Bali1

Afiliasi berasal dari OpenAlex; metadata OAI-PMH jurnal tidak memuatnya. Penulis tanpa ID OpenAlex dicocokkan berdasarkan nama, sehingga dua orang bisa tergabung atau satu orang bisa terpisah.

Sumber metadata: OAI-PMH (metadata jurnal) https://ojs2.pnb.ac.id/index.php/MATRIX/oai, pertama di-harvest 19 Nov 2026, terakhir terlihat 19 Nov 2026.
Metadata asli (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/  http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
	<dc:title xml:lang="en-US">The grounding resistance improvement of distribution substation using multiple rods and wood charcoal as soil treatment</dc:title>
	<dc:creator>Karmiathi, Ni Made</dc:creator>
	<dc:creator>Puja Yoga, Putu Martin </dc:creator>
	<dc:subject xml:lang="en-US">charcoal</dc:subject>
	<dc:subject xml:lang="en-US">electrode rod</dc:subject>
	<dc:subject xml:lang="en-US">grounding resistance</dc:subject>
	<dc:description xml:lang="en-US">The grounding system plays the important role in securing the electric power system. Low grounding resistance ensures the proper operation of the grounding system. The lower the grounding resistance value, the easier current flow through the earth without any obstacles then prevents equipment from being damaged or causing the injury of personnel. According to the PUIL 2000 standard, grounding resistance should be less than 5Ω. Methods that can be performed to reduce grounding resistance are increasing the length and diameter of the grounding rod, using multiple rods, and treating the soil to reduce its resistivity. In this study, we would like to improve the grounding system of the KA2317 distribution substation located at Mertasari, Jimbaran in South Kuta, Bali which has a grounding resistance of 8.1Ω (more than 5Ω). The method that was applied in this study was grounding improvement by adding an electrode rod and adding wood charcoal to reduce soil resistivity. At the end of the study, grounding resistance can be reduced from 8.1Ω to 1.9 Ω or improved by 76.6%.</dc:description>
	<dc:publisher xml:lang="en-US">Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali</dc:publisher>
	<dc:date>2023-03-30</dc:date>
	<dc:type>info:eu-repo/semantics/article</dc:type>
	<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
	<dc:type xml:lang="en-US">Peer-reviewed Article</dc:type>
	<dc:format>application/pdf</dc:format>
	<dc:identifier>https://ojs2.pnb.ac.id/index.php/MATRIX/article/view/963</dc:identifier>
	<dc:identifier>10.31940/matrix.v13i1.33-41</dc:identifier>
	<dc:source xml:lang="en-US">Matrix : Jurnal Manajemen Teknologi dan Informatika; Vol. 13 No. 1 (2023): Matrix: Jurnal Manajemen Teknologi dan Informatika; 33-41</dc:source>
	<dc:source>2580-5630</dc:source>
	<dc:source>2088-284X</dc:source>
	<dc:source>10.31940/matrix.v13i1</dc:source>
	<dc:language>eng</dc:language>
	<dc:relation>https://ojs2.pnb.ac.id/index.php/MATRIX/article/view/963/515</dc:relation>
	<dc:rights xml:lang="en-US">Copyright (c) 2023 Matrix : Jurnal Manajemen Teknologi dan Informatika</dc:rights>
	<dc:rights xml:lang="en-US">https://scholar.google.co.id/citations?user=NDE5gXYAAAAJ&amp;hl=id</dc:rights>
</oai_dc:dc>