Techno-Economic and Environmental Assessment of A Hybrid Solar Power System for The Kakatua Laboratory Building Using Helioscope Simulation
Scientific Contributions Oil and Gas · Vol. 49 No. 4 (2026) · hlm. 49–65
- ISSN
- 2541-0520, 2089-3361
- Terbit
- 2026-11-10
- Penerbit
- Testing Center for Oil and Gas LEMIGAS
Abstrak
This study evaluates a 12.60 kWp hybrid photovoltaic (PV)–battery system for the oil and gas laboratory in the Kakatua Building, Minas, Riau, using HelioScope. The system combines 18 N-type 700 W modules, a 10 kW hybrid inverter, and a 12.8 kWh/7.68 kW lithium iron phosphate battery supplying a 5.94 kW critical-load subset of the 8.81 kW load. The first-year AC yield is 17,546.9 kWh, giving a specific yield of 1,392.6 kWh/kWp, a performance ratio of 79.8%, and a capacity factor of 15.9%. Battery autonomy is 1.8 h at the nameplate critical load and 3.6 h at duty-weighted demand. For an investment of Rp 274.3 million and first-year savings of Rp 25.35 million, the simple payback period is 12.1 years. At a 10% discount rate and 5% annual tariff escalation over 25 years, the net present value (NPV) is −Rp 9.4 million, the internal rate of return (IRR) 9.6%, the benefit–cost ratio 0.97, and the discounted levelized cost of electricity Rp 2,229/kWh. PV alone is viable (NPV Rp 122.0 million; IRR 16.5%), so the battery is justified by power continuity rather than energy savings. The system avoids 14.62 t CO₂ in the first year and about 346 t over 25 years.