Iterative single-ended fault location in isolated neutral 6–35 kV networks

  • A. I. Uspanova
  • S. K. Sheryazov
  • Igor Koshkin
  • Uspanov Azamat Akhmetuly
  • Arman Utegulov

Bulletin of Electrical Engineering and Informatics · Vol. 15 No. 6 (2026) · hlm. 4774–4791

DOI
10.11591/eei.v15i6.12777
ISSN
2089-3191, 2302-9285
Terbit
2026-12-01
Penerbit
Institute of Advanced Engineering and Science (IAES)
Bahasa
en
Lisensi
creativecommons.org/licenses/by-sa/4.0/

Abstrak

This paper proposes an iterative approach for accurate single-line-to-ground (SLG) fault localization in 6–35 kV distribution networks with isolated neutrals. Such faults account for approximately 80% of network disturbances and are typically associated with capacitive fault currents and transition resistances of up to 2000 Ohm. Conventional lumped-parameter representations may result in localization errors of up to 50%, primarily because distributed line capacitance is neglected. The developed approach utilizes an exact ABCD-parameter representation of the line in the zero-sequence domain, where distributed electrical parameters are explicitly considered. A least-squares estimation procedure simultaneously determines fault distance and transition resistance from single-ended voltage and current measurements, accounting for capacitive currents and measurement noise. Monte Carlo analysis yielded an average relative fault-location error of 3.13%, with individual errors ranging from 0.33% to 6.83% across the investigated transition resistance range. Further experimental validation using a 12 km, 35 kV overhead distribution line demonstrated a maximum discrepancy of 0.08 km between simulated and experimental results. Consequently, the proposed iterative approach provides accurate single-ended fault localization without requiring line disconnection, making it highly suitable for reliable fault diagnostics in modern smart-grid distribution systems.

Kata kunci

Sumber metadata: OpenAlex API (jurnal SINTA, ADR 0048) https://openalex.org/S2765016208, pertama di-harvest 22 Nov 2026, terakhir terlihat 22 Nov 2026.
Metadata asli (oai_dc)
<oai_dc:dc xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/"><dc:title xml:lang="en">Iterative single-ended fault location in isolated neutral 6–35 kV networks</dc:title><dc:creator>A. I. Uspanova</dc:creator><dc:creator>S. K. Sheryazov</dc:creator><dc:creator>Igor Koshkin</dc:creator><dc:creator>Uspanov Azamat Akhmetuly</dc:creator><dc:creator>Arman Utegulov</dc:creator><dc:subject>single-phase grounding fault</dc:subject><dc:subject>fault location</dc:subject><dc:subject>isolated neutral</dc:subject><dc:subject>ABCD parameters</dc:subject><dc:subject>transition resistance</dc:subject><dc:subject>least squares estimation</dc:subject><dc:description xml:lang="en">This paper proposes an iterative approach for accurate single-line-to-ground (SLG) fault localization in 6–35 kV distribution networks with isolated neutrals. Such faults account for approximately 80% of network disturbances and are typically associated with capacitive fault currents and transition resistances of up to 2000 Ohm. Conventional lumped-parameter representations may result in localization errors of up to 50%, primarily because distributed line capacitance is neglected. The developed approach utilizes an exact ABCD-parameter representation of the line in the zero-sequence domain, where distributed electrical parameters are explicitly considered. A least-squares estimation procedure simultaneously determines fault distance and transition resistance from single-ended voltage and current measurements, accounting for capacitive currents and measurement noise. Monte Carlo analysis yielded an average relative fault-location error of 3.13%, with individual errors ranging from 0.33% to 6.83% across the investigated transition resistance range. Further experimental validation using a 12 km, 35 kV overhead distribution line demonstrated a maximum discrepancy of 0.08 km between simulated and experimental results. Consequently, the proposed iterative approach provides accurate single-ended fault localization without requiring line disconnection, making it highly suitable for reliable fault diagnostics in modern smart-grid distribution systems.</dc:description><dc:publisher>Institute of Advanced Engineering and Science (IAES)</dc:publisher><dc:date>2026-12-01</dc:date><dc:type>info:eu-repo/semantics/article</dc:type><dc:format>application/pdf</dc:format><dc:identifier>https://doi.org/10.11591/eei.v15i6.12777</dc:identifier><dc:identifier>10.11591/eei.v15i6.12777</dc:identifier><dc:source>Bulletin of Electrical Engineering and Informatics; Vol 15 No 6 (2026); 4774-4791</dc:source><dc:source>2089-3191</dc:source><dc:source>2302-9285</dc:source><dc:language>en</dc:language><dc:relation>https://beei.org/index.php/EEI/article/download/12777/5142</dc:relation><dc:rights>https://creativecommons.org/licenses/by-sa/4.0/</dc:rights></oai_dc:dc>