Analysis of Differential Relay Performance in the Bakaru Hydroelectric Power Transformer Protection System

Analisis Kinerja Relai Diferensial Pada Sistem Proteksi Transformator Daya PLTA Bakaru

Jurnal Eksitasi · Vol. 2 No. 2 (2023) · pp. 1–13

ISSN
2829-5110
Published
2023-12-26
Publisher
Departemen Teknik Elektro
Language
id

Abstract

English

A differential relay is a piece of equipment installed on both terminals of a power transformer coil to detect abnormal operating conditions in a power plant. Its function is to detect disproportionate differences in current flowing at both ends of the power transformer coil terminals as an indicator of a disturbance in the power transformer. Next, it sends a signal to the power breaker, thereby cutting off the power supply to the power transformer. This research aims to determine the correct way to set the differential relay, based on its characteristics so that it can work accurately according to its function. Determining the differential relay settings using the steep point slope. From the analysis, it was found that the slope 1 setting was 9.51% and slope 2 was 19.02%, while the installed data (existing) setting slope 1 was 8.87% and slope 2 was 17.74%. Based on determining the differential relay settings using steep point slopes through analysis and existing data on the power transformer, it was found that the differential relay settings from the analysis results were more sensitive with an angle of 5.43° than the installed settings with an angle of 5.02°. Then, when simulated in the ETAP 19.0.1 software, internal and external three-phase short circuit fault currents were obtained, where during an internal short circuit fault, the differential relay on the Bakaru PLTA power transformer immediately worked to detect abnormal conditions/faults in the transformer, whereas in external short circuit fault, the differential relay does not work detecting an abnormal condition/fault outside its working area

Bahasa Indonesia

Relai diferensial adalah salah satu peralatan yang dipasang pada kedua terminal kumparan transformator daya untuk mendeteksi keadaan operasi abnormal dalam suatu pembangkit listirk. Fungsinya mendeteksi perbedaan arus yang tidak proporsional yang mengalir pada kedua ujung terminal kumparan transformator daya sebagai indikator adanya gangguan pada transformator daya. Selanjutnya mengirim sinyal ke pemutus daya, sehingga memutuskan suplai daya pada transformator daya. Penelitian ini bertujuan menentukan cara setting relai diferensial yang tepat, berdasarkan karakteristiknya agar dapat bekerja secara akurat sesuai fungsinya. Penentuan setting relai diferensial menggunakan slope titik curam. Secara analisis didapatkan setting slope 1 sebesar 9,51% dan slope 2 sebesar 19,02% sementara data terpasang (existing) setting slope 1 sebesar 8,87% dan slope 2 sebesar 17,74%. Berdasarkan penentuan setting relai diferensial menggunakan slope titik curam secara analisis dan data terpasang (existing) pada transformator daya, diperoleh bahwa setting relai diferensial dari hasil analisis lebih sensitif dengan sudut 5,43° dari setting terpasang dengan sudut 5,02°. Kemudian saat disimulasikan pada software ETAP 19.0.1, diperoleh arus gangguan hubung singkat tiga fasa internal dan eksternal, dimana pada saat gangguan hubung singkat internal, relai diferensial pada transformator daya PLTA Bakaru langsung bekerja mendeteksi adanya kondisi abnormal/gangguan di dalam trafo, sedangkan pada gangguan hubung singkat eksternal, relai diferensial tidak bekerja mendeteksi adanya kondisi abnormal/gangguan diluar daerah kerjanya

Keywords

Collaboration network of the authors

15 authors · 24 co-authorship links

Hover or tap a name to highlight its co-authors. Double-click to open the author's page.

  • Affiliation unknown
  • Different organisations
  • Same organisation
  • Affiliation unknown
  • Thicker line = more joint articles · bigger circle = more articles
Show as table
Co-authorOrganisationJoint articles
Zaenab MusliminAffiliation unknown3
Yusri Syam AkilAffiliation unknown2
Abd RahimAffiliation unknown2
Muammar Fadli NurAffiliation unknown1
Fikran FauzyAffiliation unknown1
Intan Sari AreniAffiliation unknown1
Harits Ghazy RamadhanAffiliation unknown1
Muhammad Zhahran Zhafirin IrawanAffiliation unknown1
Muhammad Irsan SadriAffiliation unknown1
Firda Fajryani KamilAffiliation unknown1
Sri Mawar SaidAffiliation unknown1
Fatimah Az-zahraAffiliation unknown1

Affiliations come from OpenAlex; journal OAI-PMH metadata carries none. Authors without an OpenAlex ID are matched by name, which can merge or split people.

Metadata source: OAI-PMH (metadata jurnal) https://journal.unhas.ac.id/index.php/eksitasi/oai, first harvested 2 Nov 2026, last seen 2 Nov 2026.
Original metadata (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/  http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
	<dc:title xml:lang="en">Analysis of Differential Relay Performance in the Bakaru Hydroelectric Power Transformer Protection System</dc:title>
	<dc:title xml:lang="id">Analisis Kinerja Relai Diferensial Pada Sistem Proteksi Transformator Daya PLTA Bakaru</dc:title>
	<dc:creator xml:lang="en">Indar Chaerah Gunadin</dc:creator>
	<dc:creator xml:lang="en">Yustinus Upa Sombolayuk </dc:creator>
	<dc:creator xml:lang="en">Caesar William Alexander</dc:creator>
	<dc:creator xml:lang="id">Indar Chaerah Gunadin</dc:creator>
	<dc:creator xml:lang="id">Yustinus Upa Sombolayuk </dc:creator>
	<dc:creator xml:lang="id">Caesar William Alexander</dc:creator>
	<dc:subject xml:lang="en">Fault detection</dc:subject>
	<dc:subject xml:lang="en">Power Transformer</dc:subject>
	<dc:subject xml:lang="en">Slope</dc:subject>
	<dc:subject xml:lang="en">Differential Relay</dc:subject>
	<dc:subject xml:lang="en">ETAP Simulation</dc:subject>
	<dc:subject xml:lang="id">Deteksi gangguan</dc:subject>
	<dc:subject xml:lang="id">Transformator Daya</dc:subject>
	<dc:subject xml:lang="id">Slope</dc:subject>
	<dc:subject xml:lang="id">Relai Diferensial</dc:subject>
	<dc:subject xml:lang="id">Simulasi ETAP</dc:subject>
	<dc:description xml:lang="en">A differential relay is a piece of equipment installed on both terminals of a power transformer coil to detect abnormal operating conditions in a power plant. Its function is to detect disproportionate differences in current flowing at both ends of the power transformer coil terminals as an indicator of a disturbance in the power transformer. Next, it sends a signal to the power breaker, thereby cutting off the power supply to the power transformer. This research aims to determine the correct way to set the differential relay, based on its characteristics so that it can work accurately according to its function. Determining the differential relay settings using the steep point slope. From the analysis, it was found that the slope 1 setting was 9.51% and slope 2 was 19.02%, while the installed data (existing) setting slope 1 was 8.87% and slope 2 was 17.74%. Based on determining the differential relay settings using steep point slopes through analysis and existing data on the power transformer, it was found that the differential relay settings from the analysis results were more sensitive with an angle of 5.43° than the installed settings with an angle of 5.02°. Then, when simulated in the ETAP 19.0.1 software, internal and external three-phase short circuit fault currents were obtained, where during an internal short circuit fault, the differential relay on the Bakaru PLTA power transformer immediately worked to detect abnormal conditions/faults in the transformer, whereas in external short circuit fault, the differential relay does not work detecting an abnormal condition/fault outside its working area</dc:description>
	<dc:description xml:lang="id">Relai diferensial adalah salah satu peralatan yang dipasang pada kedua terminal kumparan transformator daya untuk mendeteksi keadaan operasi abnormal dalam suatu pembangkit listirk. Fungsinya mendeteksi perbedaan arus yang tidak proporsional yang mengalir pada kedua ujung terminal kumparan transformator daya sebagai indikator adanya gangguan pada transformator daya. Selanjutnya mengirim sinyal ke pemutus daya, sehingga memutuskan suplai daya pada transformator daya. Penelitian ini bertujuan menentukan cara setting relai diferensial yang tepat, berdasarkan karakteristiknya agar dapat bekerja secara akurat sesuai fungsinya. Penentuan setting relai diferensial menggunakan slope titik curam. Secara analisis didapatkan setting slope 1 sebesar 9,51% dan slope 2 sebesar 19,02% sementara data terpasang (existing) setting slope 1 sebesar 8,87% dan slope 2 sebesar 17,74%. Berdasarkan penentuan setting relai diferensial menggunakan slope titik curam secara analisis dan data terpasang (existing) pada transformator daya, diperoleh bahwa setting relai diferensial dari hasil analisis lebih sensitif dengan sudut 5,43° dari setting terpasang dengan sudut 5,02°. Kemudian saat disimulasikan pada software ETAP 19.0.1, diperoleh arus gangguan hubung singkat tiga fasa internal dan eksternal, dimana pada saat gangguan hubung singkat internal, relai diferensial pada transformator daya PLTA Bakaru langsung bekerja mendeteksi adanya kondisi abnormal/gangguan di dalam trafo, sedangkan pada gangguan hubung singkat eksternal, relai diferensial tidak bekerja mendeteksi adanya kondisi abnormal/gangguan diluar daerah kerjanya</dc:description>
	<dc:publisher xml:lang="id">Departemen Teknik Elektro</dc:publisher>
	<dc:date>2023-12-26</dc:date>
	<dc:type>info:eu-repo/semantics/article</dc:type>
	<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
	<dc:type xml:lang="id">Artikel Peer-review</dc:type>
	<dc:format>application/pdf</dc:format>
	<dc:identifier>https://journal.unhas.ac.id/index.php/eksitasi/article/view/32483</dc:identifier>
	<dc:source xml:lang="en">Jurnal Eksitasi; Vol. 2 No. 2 (2023): Jurnal Eksitasi Departemen Teknik Elektro Vol. 2. No.2. 2023; 1 - 13</dc:source>
	<dc:source xml:lang="id">JURNAL EKSITASI DEPARTEMEN TEKNIK ELEKTRO; Vol 2 No 2 (2023): Jurnal Eksitasi Departemen Teknik Elektro Vol. 2. No.2. 2023; 1 - 13</dc:source>
	<dc:source>2829-5110</dc:source>
	<dc:language>id</dc:language>
	<dc:relation>https://journal.unhas.ac.id/index.php/eksitasi/article/view/32483/10988</dc:relation>
</oai_dc:dc>