Transmission line short circuit analysis by impedance matrix method

International Journal of Electrical and Computer Engineering (IJECE) · Vol. 10 No. 2 (2020)

DOI
10.11591/ijece.v10i2.pp1712-1721
ISSN
2088-8708, 2088-8708
Published
2020-04-01
Publisher
Institute of Advanced Engineering and Science
License
creativecommons.org/licenses/by-nc/4.0

Abstract

Fault analysis is the process of determining the magnitude of fault voltage and current during the occurrence of different types of fault in electrical power system. Transmission line fault analysis is usually done for both symmetrical and unsymmetrical faults. Symmetrical faults are called three-phase balance fault while unsymmetrical faults include: single line-to-ground, line-to-line, and double line-to-ground faults. In this research, bus impedance matrix method for fault analysis is presented. Bus impedance matrix approach has several advantages over Thevenin’s equivalent method and other conventional approaches. This is because the off-diagonal elements represent the transfer impedance of the power system network and helps in calculating the branch fault currents during a fault. Analytical and simulation approaches on a single line-to-ground fault on 3-bus power system network under bolted fault condition were used for the study. Both methods were compared and result showed negligible deviation of 0.02% on the average. The fault currents under bolted condition for the single line-to-ground fault were found to be 4. 7244p.u while the bus voltage is 0. 4095p.u for buses 1 and 2 respectively and 0. 00p.u for bus 3 since the fault occurred at this bus. Therefore, there is no need of burdensomely connecting the entire three sequence network during fault analysis in electrical power system.

Collaboration network of the authors

8 authors · 16 co-authorship links · 4 across different organisations

Hover or tap a name to highlight its co-authors. Double-click to open the author's page.

  • University of Nigeria
  • Enugu State University of Science and Technology
  • Affiliation unknown
  • Different organisations
  • Same organisation
  • Affiliation unknown
  • Thicker line = more joint articles · bigger circle = more articles
Show as table
Co-authorOrganisationJoint articles
Kenneth Chijioke ChikeUniversity of Nigeria2
Jean Felix ManirakizaAffiliation unknown1
Prince Anthony OkoroUniversity of Nigeria1
Princewill C. EneEnugu State University of Science and Technology1
Amanze C. FortuneUniversity of Nigeria1
Luke Uwakwe OmejeUniversity of Nigeria1

Affiliations come from OpenAlex; journal OAI-PMH metadata carries none. Authors without an OpenAlex ID are matched by name, which can merge or split people.

This record comes from Crossref (what the publisher deposited), because the journal's own OAI-PMH endpoint could not be harvested.

Metadata source: Crossref API (cadangan, berdasarkan ISSN) https://api.crossref.org/journals/2088-8708/works, first harvested 27 Okt 2026, last seen 27 Okt 2026.
Metadata as oai_dc, converted from Crossref
<oai_dc:dc xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/"><dc:title>Transmission line short circuit analysis by impedance matrix method</dc:title><dc:creator>Anyaka, Boniface Onyemaechi</dc:creator><dc:creator>Ozioko, Innocent Onyebuchi</dc:creator><dc:description>&lt;jats:p&gt;Fault analysis is the process of determining the magnitude of fault voltage and current during the occurrence of different types of fault in electrical power system. Transmission line fault analysis is usually done for both symmetrical and unsymmetrical faults. Symmetrical faults are called three-phase balance fault while unsymmetrical faults include: single line-to-ground, line-to-line, and double line-to-ground faults. In this research, bus impedance matrix method for fault analysis is presented. Bus impedance matrix approach has several advantages over Thevenin’s equivalent method and other conventional approaches. This is because the off-diagonal elements represent the transfer impedance of the power system network and helps in calculating the branch fault currents during a fault. Analytical and simulation approaches on a single line-to-ground fault on 3-bus power system network under bolted fault condition were used for the study. Both methods were compared and result showed negligible deviation of 0.02% on the average. The fault currents under bolted condition for the single line-to-ground fault were found to be 4. 7244p.u while the bus voltage is 0. 4095p.u for buses 1 and 2 respectively and 0. 00p.u for bus 3 since the fault occurred at this bus. Therefore, there is no need of burdensomely connecting the entire three sequence network during fault analysis in electrical power system.&lt;/jats:p&gt;</dc:description><dc:publisher>Institute of Advanced Engineering and Science</dc:publisher><dc:date>2020-04-01</dc:date><dc:type>info:eu-repo/semantics/article</dc:type><dc:format>application/pdf</dc:format><dc:identifier>https://doi.org/10.11591/ijece.v10i2.pp1712-1721</dc:identifier><dc:identifier>10.11591/ijece.v10i2.pp1712-1721</dc:identifier><dc:source>International Journal of Electrical and Computer Engineering (IJECE); Vol 10 No 2 (2020); 1712</dc:source><dc:source>2088-8708</dc:source><dc:source>2088-8708</dc:source><dc:relation>http://ijece.iaescore.com/index.php/IJECE/article/viewFile/16910/pdf</dc:relation><dc:rights>http://creativecommons.org/licenses/by-nc/4.0</dc:rights></oai_dc:dc>