Performance Analysis Of Centrifugal End Suction Pump And Three Phase Induction Motor In The Distribution Pumping Station of PDAM Tirta Mountala, Aceh Besar Regency

Circuit: Jurnal Ilmiah Pendidikan Teknik Elektro · Vol. 9 No. 1 (2025) · hlm. 65–84

DOI
10.22373/crc.v9i1.27241
ISSN
2549-3701, 2549-3698
Terbit
2025-01-23
Penerbit
PTE FTK UIN Ar-Raniry
Bahasa
eng
Lisensi
creativecommons.org/licenses/by-sa/4.0

Abstrak

This study evaluates the efficiency performance of the motor-pump system used by the regional water utility company to identify strategies for improving efficiency. The three-phase induction motor utilized is highly dependent on the quality of the supplied voltage. The primary focus of this research includes analyzing the efficiency performance of the system, examining the electrical parameters of the three-phase induction motor, which include voltage and current imbalance, power factor, and Specific Energy Consumption (SEC). Another focus is the optimization of the motor-pump system and estimating the potential energy savings and operational cost reductions achievable within one year. The research method involves measuring electrical and hydraulic parameters. Electrical parameters were measured using a 3-phase power analyzer (type DW-6195), which records current, voltage, frequency, power, and power factor. Hydraulic parameters were measured using an electromagnetic flow meter for flow rate readings, a manometer for pressure measurements, and a measuring tape to measure the water level in the reservoir tank. All measurement results were tabulated and further analyzed to evaluate the performance of electrical parameters and compare them to the hydraulic performance of the system. The results revealed that the efficiency of the PDAM motor-pump system is below 50%, indicating the need for a comprehensive system revitalization. An inspection of electrical parameters showed that voltage deviation is below 10%, voltage imbalance is below 5%, and current imbalance ranges between 5.65% and 7.35%. All electrical parameters comply with IEEE standards. The power factor, at 0.85, also meets electrical standards. The SEC value, below 0.44 kWh/m³, indicates potential energy efficiency. Based on the pump performance curve study, the pump system can be replaced with a pump unit that has a lower electrical power rating, reducing it from 75 kW to 55 kW, while maintaining its hydraulic performance. Implementing this revitalization is expected to save up to 172,800 kWh of energy per motor per year and reduce by 18.4%.

Kata kunci

Jaringan kolaborasi para penulis

40 penulis · 90 tautan kepenulisan bersama · 32 lintas organisasi · menampilkan 40 yang paling banyak terhubung

Arahkan kursor atau ketuk sebuah nama untuk menyorot rekan penulisnya. Klik dua kali untuk membuka halaman penulis.

  • Universitas Islam Negeri Ar-Raniry
  • Universitas Syiah Kuala
  • Poltekkes Kemenkes Banjarmasin
  • Universitas Teuku Umar
  • Universitas Bina Darma
  • Sunan Kalijaga State Islamic University Yogyakarta
  • Universitas Gadjah Mada
  • Organisasi lain
  • Afiliasi tidak diketahui
  • Organisasi berbeda
  • Organisasi sama
  • Afiliasi tidak diketahui
  • Garis lebih tebal = lebih banyak artikel bersama · lingkaran lebih besar = lebih banyak artikel
Tampilkan sebagai tabel
Rekan penulisOrganisasiArtikel bersama
Fathiah FathiahUniversitas Islam Negeri Ar-Raniry3
Muhammad Rizal FachriUniversitas Islam Negeri Ar-Raniry2
Basrul BasrulUniversitas Islam Negeri Ar-Raniry2
Rezqi MaliaUniversitas Teuku Umar2
Ima DwitawatiUniversitas Islam Negeri Ar-Raniry2
Laila SholehahPoltekkes Kemenkes Banjarmasin2
Aprianti ApriantiPoltekkes Kemenkes Banjarmasin2
Arika Dhien SartikaAfiliasi tidak diketahui2
Dedy SyamsuarUniversitas Bina Darma1
Chairunnisa DjayadinSunan Kalijaga State Islamic University Yogyakarta1
Nafisah HanimUniversitas Islam Negeri Ar-Raniry1
Eriawati EriawatiUniversitas Islam Negeri Ar-Raniry1
Hadi KurniawanUniversitas Islam Negeri Ar-Raniry1
Aris MunandarUniversitas Gadjah Mada1
Khairan ARUniversitas Islam Negeri Ar-Raniry1
Mawardi MawardiUniversitas Islam Negeri Ar-Raniry1
Malahayati UmarUniversitas Islam Negeri Ar-Raniry1
Mouliza AstariUniversitas Islam Negeri Ar-Raniry1
Anjar Purba AsmaraUniversitas Islam Negeri Ar-Raniry1
Nurhayati NurhayatiUniversitas Islam Negeri Ar-Raniry1
Fitra SaputraUniversitas Islam Negeri Ar-Raniry1
Radhiah RadhiahPoliteknik Negeri Lhokseumawe1
Mursyidin MursyidinUniversitas Islam Negeri Ar-Raniry1
Umrah HayaniAfiliasi tidak diketahui1
Hari Anna LastyaUniversitas Islam Negeri Ar-Raniry1
Abrar Syahrul FajriUniversitas Islam Negeri Ar-Raniry1
Muhammad Zaki FuadiUniversitas Islam Negeri Ar-Raniry1
Irfan Murti RaaziUniversitas Islam Negeri Ar-Raniry1
Mulkan FadhliUniversitas Islam Negeri Ar-Raniry1
Akhyar AkhyarSekolah Tinggi Agama Islam Negeri Mandailing Natal1
Amien Refnas RaisUniversitas Islam Negeri Ar-Raniry1
Suhir ArdiansyahUniversidad Central de Venezuela1
Hendri AhmadianUniversitas Islam Negeri Ar-Raniry1

Afiliasi berasal dari OpenAlex; metadata OAI-PMH jurnal tidak memuatnya. Penulis tanpa ID OpenAlex dicocokkan berdasarkan nama, sehingga dua orang bisa tergabung atau satu orang bisa terpisah.

Sumber metadata: OAI-PMH (metadata jurnal) https://jurnal.ar-raniry.ac.id/index.php/circuit/oai, pertama di-harvest 6 Nov 2026, terakhir terlihat 8 Nov 2026.
Metadata asli (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/  http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
	<dc:title xml:lang="en">Performance Analysis Of Centrifugal End Suction Pump And Three Phase Induction Motor In The Distribution Pumping Station of PDAM Tirta Mountala, Aceh Besar Regency</dc:title>
	<dc:creator xml:lang="en">Fathurrahman, Fathurrahman</dc:creator>
	<dc:creator xml:lang="en">Akbar, Habibi</dc:creator>
	<dc:creator xml:lang="en">Siregar, Ramdhan Halid</dc:creator>
	<dc:creator xml:lang="en">Utami, Rika Sri</dc:creator>
	<dc:creator xml:lang="en">Syukri, Mahdi</dc:creator>
	<dc:creator xml:lang="en">Fachri, Muhammad Rizal</dc:creator>
	<dc:creator xml:lang="en">Malahayati, Malahayati</dc:creator>
	<dc:subject xml:lang="en">Three-phase induction motor</dc:subject>
	<dc:subject xml:lang="en">centrifugal pump end-suction</dc:subject>
	<dc:subject xml:lang="en">energy efficiency</dc:subject>
	<dc:subject xml:lang="en">Specific Energy Consumption.</dc:subject>
	<dc:subject xml:lang="en">Electrical Machenery</dc:subject>
	<dc:description xml:lang="en">This study evaluates the efficiency performance of the motor-pump system used by the regional water utility company to identify strategies for improving efficiency. The three-phase induction motor utilized is highly dependent on the quality of the supplied voltage. The primary focus of this research includes analyzing the efficiency performance of the system, examining the electrical parameters of the three-phase induction motor, which include voltage and current imbalance, power factor, and Specific Energy Consumption (SEC). Another focus is the optimization of the motor-pump system and estimating the potential energy savings and operational cost reductions achievable within one year. The research method involves measuring electrical and hydraulic parameters. Electrical parameters were measured using a 3-phase power analyzer (type DW-6195), which records current, voltage, frequency, power, and power factor. Hydraulic parameters were measured using an electromagnetic flow meter for flow rate readings, a manometer for pressure measurements, and a measuring tape to measure the water level in the reservoir tank. All measurement results were tabulated and further analyzed to evaluate the performance of electrical parameters and compare them to the hydraulic performance of the system. The results revealed that the efficiency of the PDAM motor-pump system is below 50%, indicating the need for a comprehensive system revitalization. An inspection of electrical parameters showed that voltage deviation is below 10%, voltage imbalance is below 5%, and current imbalance ranges between 5.65% and 7.35%. All electrical parameters comply with IEEE standards. The power factor, at 0.85, also meets electrical standards. The SEC value, below 0.44 kWh/m³, indicates potential energy efficiency. Based on the pump performance curve study, the pump system can be replaced with a pump unit that has a lower electrical power rating, reducing it from 75 kW to 55 kW, while maintaining its hydraulic performance. Implementing this revitalization is expected to save up to 172,800 kWh of energy per motor per year and reduce by 18.4%.</dc:description>
	<dc:publisher xml:lang="en">PTE FTK UIN Ar-Raniry</dc:publisher>
	<dc:date>2025-01-23</dc:date>
	<dc:type>info:eu-repo/semantics/article</dc:type>
	<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
	<dc:format>application/pdf</dc:format>
	<dc:identifier>https://jurnal.ar-raniry.ac.id/index.php/circuit/article/view/27241</dc:identifier>
	<dc:identifier>10.22373/crc.v9i1.27241</dc:identifier>
	<dc:source xml:lang="en">Circuit: Jurnal Ilmiah Pendidikan Teknik Elektro; Vol. 9 No. 1 (2025); 65-84</dc:source>
	<dc:source>2549-3701</dc:source>
	<dc:source>2549-3698</dc:source>
	<dc:language>eng</dc:language>
	<dc:relation>https://jurnal.ar-raniry.ac.id/index.php/circuit/article/view/27241/10594</dc:relation>
	<dc:rights xml:lang="en">Copyright (c) 2025 Fathurrahman, Habibi Akbar, Ramdhan Halid Siregar, Rika Sri Utami, Mahdi Syukri, Muhammad Rizal Fachri, Malahayati</dc:rights>
	<dc:rights xml:lang="en">http://creativecommons.org/licenses/by-sa/4.0</dc:rights>
</oai_dc:dc>