Journal
SINTA 3
The grounding resistance improvement of distribution substation using multiple rods and wood charcoal as soil treatment
Matrix: Jurnal Manajemen Teknologi dan Informatika · Vol. 13 No. 1 (2023) · pp. 33–41
ISSN 2580-5630, 2088-284X
Published 2023-03-30
Publisher Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali
Language eng
Abstract
The grounding system plays the important role in securing the electric power system. Low grounding resistance ensures the proper operation of the grounding system. The lower the grounding resistance value, the easier current flow through the earth without any obstacles then prevents equipment from being damaged or causing the injury of personnel. According to the PUIL 2000 standard, grounding resistance should be less than 5Ω. Methods that can be performed to reduce grounding resistance are increasing the length and diameter of the grounding rod, using multiple rods, and treating the soil to reduce its resistivity. In this study, we would like to improve the grounding system of the KA2317 distribution substation located at Mertasari, Jimbaran in South Kuta, Bali which has a grounding resistance of 8.1Ω (more than 5Ω). The method that was applied in this study was grounding improvement by adding an electrode rod and adding wood charcoal to reduce soil resistivity. At the end of the study, grounding resistance can be reduced from 8.1Ω to 1.9 Ω or improved by 76.6%.
Collaboration network of the authors
5 authors ·
5 co-authorship links
Hover or tap a name to highlight its co-authors. Double-click to open the author's page.
Different organisations
Same organisation
Affiliation unknown
Thicker line = more joint articles · bigger circle = more articles
Show as table
Affiliations come from OpenAlex; journal OAI-PMH metadata carries none. Authors without an OpenAlex ID are matched by name, which can merge or split people.
Metadata source: OAI-PMH (metadata jurnal) https://ojs2.pnb.ac.id/index.php/MATRIX/oai, first harvested 19 Nov 2026, last seen 19 Nov 2026.
Original metadata (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/ http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
<dc:title xml:lang="en-US">The grounding resistance improvement of distribution substation using multiple rods and wood charcoal as soil treatment</dc:title>
<dc:creator>Karmiathi, Ni Made</dc:creator>
<dc:creator>Puja Yoga, Putu Martin </dc:creator>
<dc:subject xml:lang="en-US">charcoal</dc:subject>
<dc:subject xml:lang="en-US">electrode rod</dc:subject>
<dc:subject xml:lang="en-US">grounding resistance</dc:subject>
<dc:description xml:lang="en-US">The grounding system plays the important role in securing the electric power system. Low grounding resistance ensures the proper operation of the grounding system. The lower the grounding resistance value, the easier current flow through the earth without any obstacles then prevents equipment from being damaged or causing the injury of personnel. According to the PUIL 2000 standard, grounding resistance should be less than 5Ω. Methods that can be performed to reduce grounding resistance are increasing the length and diameter of the grounding rod, using multiple rods, and treating the soil to reduce its resistivity. In this study, we would like to improve the grounding system of the KA2317 distribution substation located at Mertasari, Jimbaran in South Kuta, Bali which has a grounding resistance of 8.1Ω (more than 5Ω). The method that was applied in this study was grounding improvement by adding an electrode rod and adding wood charcoal to reduce soil resistivity. At the end of the study, grounding resistance can be reduced from 8.1Ω to 1.9 Ω or improved by 76.6%.</dc:description>
<dc:publisher xml:lang="en-US">Unit Publikasi Ilmiah, P3M, Politeknik Negeri Bali</dc:publisher>
<dc:date>2023-03-30</dc:date>
<dc:type>info:eu-repo/semantics/article</dc:type>
<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
<dc:type xml:lang="en-US">Peer-reviewed Article</dc:type>
<dc:format>application/pdf</dc:format>
<dc:identifier>https://ojs2.pnb.ac.id/index.php/MATRIX/article/view/963</dc:identifier>
<dc:identifier>10.31940/matrix.v13i1.33-41</dc:identifier>
<dc:source xml:lang="en-US">Matrix : Jurnal Manajemen Teknologi dan Informatika; Vol. 13 No. 1 (2023): Matrix: Jurnal Manajemen Teknologi dan Informatika; 33-41</dc:source>
<dc:source>2580-5630</dc:source>
<dc:source>2088-284X</dc:source>
<dc:source>10.31940/matrix.v13i1</dc:source>
<dc:language>eng</dc:language>
<dc:relation>https://ojs2.pnb.ac.id/index.php/MATRIX/article/view/963/515</dc:relation>
<dc:rights xml:lang="en-US">Copyright (c) 2023 Matrix : Jurnal Manajemen Teknologi dan Informatika</dc:rights>
<dc:rights xml:lang="en-US">https://scholar.google.co.id/citations?user=NDE5gXYAAAAJ&hl=id</dc:rights>
</oai_dc:dc>
Citations and indexing
OpenAlex
Indexed
via DOI
12 citations
Crossref
Indexed
via DOI
1 citation
Counts as reported by each index on 19 Nov 2026; indexes count citations differently.
OpenAlex also lists this work in: crossref, doaj.
Cite this article
APA 7
Karmiathi, N. M., & Puja Yoga, P. M. (2023). The grounding resistance improvement of distribution substation using multiple rods and wood charcoal as soil treatment. Matrix: Jurnal Manajemen Teknologi dan Informatika, 13(1), 33–41. https://doi.org/10.31940/matrix.v13i1.33-41
Copy
IEEE
N. M. Karmiathi and P. M. Puja Yoga, “The grounding resistance improvement of distribution substation using multiple rods and wood charcoal as soil treatment,” Matrix: Jurnal Manajemen Teknologi dan Informatika, vol. 13, no. 1, pp. 33–41, 2023, doi: 10.31940/matrix.v13i1.33-41.
Copy