Performance Analysis Of Centrifugal End Suction Pump And Three Phase Induction Motor In The Distribution Pumping Station of PDAM Tirta Mountala, Aceh Besar Regency

Circuit: Jurnal Ilmiah Pendidikan Teknik Elektro · Vol. 9 No. 1 (2025) · pp. 65–84

DOI
10.22373/crc.v9i1.27241
ISSN
2549-3701, 2549-3698
Published
2025-01-23
Publisher
PTE FTK UIN Ar-Raniry
Language
eng
License
creativecommons.org/licenses/by-sa/4.0

Abstract

This study evaluates the efficiency performance of the motor-pump system used by the regional water utility company to identify strategies for improving efficiency. The three-phase induction motor utilized is highly dependent on the quality of the supplied voltage. The primary focus of this research includes analyzing the efficiency performance of the system, examining the electrical parameters of the three-phase induction motor, which include voltage and current imbalance, power factor, and Specific Energy Consumption (SEC). Another focus is the optimization of the motor-pump system and estimating the potential energy savings and operational cost reductions achievable within one year. The research method involves measuring electrical and hydraulic parameters. Electrical parameters were measured using a 3-phase power analyzer (type DW-6195), which records current, voltage, frequency, power, and power factor. Hydraulic parameters were measured using an electromagnetic flow meter for flow rate readings, a manometer for pressure measurements, and a measuring tape to measure the water level in the reservoir tank. All measurement results were tabulated and further analyzed to evaluate the performance of electrical parameters and compare them to the hydraulic performance of the system. The results revealed that the efficiency of the PDAM motor-pump system is below 50%, indicating the need for a comprehensive system revitalization. An inspection of electrical parameters showed that voltage deviation is below 10%, voltage imbalance is below 5%, and current imbalance ranges between 5.65% and 7.35%. All electrical parameters comply with IEEE standards. The power factor, at 0.85, also meets electrical standards. The SEC value, below 0.44 kWh/m³, indicates potential energy efficiency. Based on the pump performance curve study, the pump system can be replaced with a pump unit that has a lower electrical power rating, reducing it from 75 kW to 55 kW, while maintaining its hydraulic performance. Implementing this revitalization is expected to save up to 172,800 kWh of energy per motor per year and reduce by 18.4%.

Keywords

Collaboration network of the authors

40 authors · 95 co-authorship links · 7 across different organisations · showing the 40 most connected

Hover or tap a name to highlight its co-authors. Double-click to open the author's page.

  • Sunan Kalijaga State Islamic University Yogyakarta
  • Politeknik Negeri Sriwijaya
  • Politeknik Negeri Ujung Pandang
  • Universitas Islam Negeri Ar-Raniry
  • Sekolah Tinggi Agama Islam Negeri Mandailing Natal
  • Affiliation unknown
  • Different organisations
  • Same organisation
  • Affiliation unknown
  • Thicker line = more joint articles · bigger circle = more articles
Show as table
Co-authorOrganisationJoint articles
Fathiah FathiahAffiliation unknown5
Akhyar AkhyarSekolah Tinggi Agama Islam Negeri Mandailing Natal4
Zulkarnain JalilAffiliation unknown3
Nurhayati NurhayatiPoliteknik Negeri Ujung Pandang3
Hadi KurniawanAffiliation unknown2
Rezqi MaliaAffiliation unknown2
Basrul BasrulAffiliation unknown2
Ima DwitawatiAffiliation unknown2
Mursal MursalAffiliation unknown2
Aprianti ApriantiAffiliation unknown2
Laila SholehahAffiliation unknown2
Khairan ARUniversitas Islam Negeri Ar-Raniry2
Arika Dhien SartikaAffiliation unknown2
Hari Anna LastyaAffiliation unknown2
Dedy SyamsuarPoliteknik Negeri Sriwijaya1
Chairunnisa DjayadinSunan Kalijaga State Islamic University Yogyakarta1
Chairul FahmiAffiliation unknown1
Muhammad Siddiq ArmiaAffiliation unknown1
Badri Hasan SulaimanAffiliation unknown1
EMK AlidarAffiliation unknown1
Eriawati EriawatiAffiliation unknown1
Nafisah HanimAffiliation unknown1
Hendrayana HendrayanaAffiliation unknown1
Aris MunandarAffiliation unknown1
Mawardi MawardiAffiliation unknown1
Malahayati UmarAffiliation unknown1
Mouliza AstariAffiliation unknown1
Rahmatul UmmiyaAffiliation unknown1
Anjar Purba AsmaraAffiliation unknown1
Fitra SaputraAffiliation unknown1
Radhiah RadhiahAffiliation unknown1
Mursyidin MursyidinAffiliation unknown1
Umrah HayaniAffiliation unknown1

Affiliations come from OpenAlex; journal OAI-PMH metadata carries none. Authors without an OpenAlex ID are matched by name, which can merge or split people.

Metadata source: OAI-PMH (metadata jurnal) https://jurnal.ar-raniry.ac.id/index.php/circuit/oai, first harvested 6 Nov 2026, last seen 8 Nov 2026.
Original metadata (oai_dc)
<oai_dc:dc xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/  http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
	<dc:title xml:lang="en">Performance Analysis Of Centrifugal End Suction Pump And Three Phase Induction Motor In The Distribution Pumping Station of PDAM Tirta Mountala, Aceh Besar Regency</dc:title>
	<dc:creator xml:lang="en">Fathurrahman, Fathurrahman</dc:creator>
	<dc:creator xml:lang="en">Akbar, Habibi</dc:creator>
	<dc:creator xml:lang="en">Siregar, Ramdhan Halid</dc:creator>
	<dc:creator xml:lang="en">Utami, Rika Sri</dc:creator>
	<dc:creator xml:lang="en">Syukri, Mahdi</dc:creator>
	<dc:creator xml:lang="en">Fachri, Muhammad Rizal</dc:creator>
	<dc:creator xml:lang="en">Malahayati, Malahayati</dc:creator>
	<dc:subject xml:lang="en">Three-phase induction motor</dc:subject>
	<dc:subject xml:lang="en">centrifugal pump end-suction</dc:subject>
	<dc:subject xml:lang="en">energy efficiency</dc:subject>
	<dc:subject xml:lang="en">Specific Energy Consumption.</dc:subject>
	<dc:subject xml:lang="en">Electrical Machenery</dc:subject>
	<dc:description xml:lang="en">This study evaluates the efficiency performance of the motor-pump system used by the regional water utility company to identify strategies for improving efficiency. The three-phase induction motor utilized is highly dependent on the quality of the supplied voltage. The primary focus of this research includes analyzing the efficiency performance of the system, examining the electrical parameters of the three-phase induction motor, which include voltage and current imbalance, power factor, and Specific Energy Consumption (SEC). Another focus is the optimization of the motor-pump system and estimating the potential energy savings and operational cost reductions achievable within one year. The research method involves measuring electrical and hydraulic parameters. Electrical parameters were measured using a 3-phase power analyzer (type DW-6195), which records current, voltage, frequency, power, and power factor. Hydraulic parameters were measured using an electromagnetic flow meter for flow rate readings, a manometer for pressure measurements, and a measuring tape to measure the water level in the reservoir tank. All measurement results were tabulated and further analyzed to evaluate the performance of electrical parameters and compare them to the hydraulic performance of the system. The results revealed that the efficiency of the PDAM motor-pump system is below 50%, indicating the need for a comprehensive system revitalization. An inspection of electrical parameters showed that voltage deviation is below 10%, voltage imbalance is below 5%, and current imbalance ranges between 5.65% and 7.35%. All electrical parameters comply with IEEE standards. The power factor, at 0.85, also meets electrical standards. The SEC value, below 0.44 kWh/m³, indicates potential energy efficiency. Based on the pump performance curve study, the pump system can be replaced with a pump unit that has a lower electrical power rating, reducing it from 75 kW to 55 kW, while maintaining its hydraulic performance. Implementing this revitalization is expected to save up to 172,800 kWh of energy per motor per year and reduce by 18.4%.</dc:description>
	<dc:publisher xml:lang="en">PTE FTK UIN Ar-Raniry</dc:publisher>
	<dc:date>2025-01-23</dc:date>
	<dc:type>info:eu-repo/semantics/article</dc:type>
	<dc:type>info:eu-repo/semantics/publishedVersion</dc:type>
	<dc:format>application/pdf</dc:format>
	<dc:identifier>https://jurnal.ar-raniry.ac.id/index.php/circuit/article/view/27241</dc:identifier>
	<dc:identifier>10.22373/crc.v9i1.27241</dc:identifier>
	<dc:source xml:lang="en">Circuit: Jurnal Ilmiah Pendidikan Teknik Elektro; Vol. 9 No. 1 (2025); 65-84</dc:source>
	<dc:source>2549-3701</dc:source>
	<dc:source>2549-3698</dc:source>
	<dc:language>eng</dc:language>
	<dc:relation>https://jurnal.ar-raniry.ac.id/index.php/circuit/article/view/27241/10594</dc:relation>
	<dc:rights xml:lang="en">Copyright (c) 2025 Fathurrahman, Habibi Akbar, Ramdhan Halid Siregar, Rika Sri Utami, Mahdi Syukri, Muhammad Rizal Fachri, Malahayati</dc:rights>
	<dc:rights xml:lang="en">http://creativecommons.org/licenses/by-sa/4.0</dc:rights>
</oai_dc:dc>